Failure analysis of lead-acid batteries at extreme operating temperatures

被引:2
|
作者
Prasad, Umesh [1 ]
Prakash, Jyoti [1 ]
Kannan, Arunachala Nadar M. [1 ]
Kamavaram, Venkat [2 ]
Arumugam, Ganesh K. [2 ]
机构
[1] Arizona State Univ, Polytech Sch, Ira A Fulton Sch Engn, Mesa, AZ 85212 USA
[2] Oceanit Labs, Honolulu, HI USA
来源
BATTERY ENERGY | 2023年 / 2卷 / 04期
关键词
capacity degradation; failure analysis; higher temperatures; lead acid batteries; NEGATIVE ELECTRODE; ACTIVE-MASS; CHARGE; STATE; CAPACITY;
D O I
10.1002/bte2.20230008
中图分类号
O646 [电化学、电解、磁化学];
学科分类号
081704 ;
摘要
The lead-acid battery system is designed to perform optimally at ambient temperature (25 degrees C) in terms of capacity and cyclability. However, varying climate zones enforce harsher conditions on automotive lead-acid batteries. Hence, they aged faster and showed lower performance when operated at extremity of the optimum ambient conditions. In this work, a systematic study was conducted to analyze the effect of varying temperatures (-10 degrees C, 0 degrees C, 25 degrees C, and 40 degrees C) on the sealed lead acid. Enersys (R) Cyclon (2V, 5Ah) cells were cycled at C/10 rate using a battery testing system. Environmental aging results in shorter cycle life due to the degradation of electrode and grid materials at higher temperatures (25 degrees C and 40 degrees C), while at lower temperatures (-10 degrees C and 0 degrees C), negligible degradation was observed due to slower kinetics and reduced available capacity. Electrochemical impedance spectroscopy, X-ray diffraction, and energy-dispersive X-ray spectroscopy analysis were used to evaluate the degradation mechanism and chemical and morphological changes.
引用
下载
收藏
页数:11
相关论文
共 50 条
  • [1] LEAD-ACID BATTERIES
    MINTER, RW
    ELECTRONICS AND POWER, 1970, 16 (JAN): : 28 - &
  • [2] Optimized lead-acid grid architectures for automotive lead-acid batteries: An electrochemical analysis
    Calborean, Adrian
    Murariu, Teodora
    Morari, Cristian
    ELECTROCHIMICA ACTA, 2021, 372
  • [3] ANALYSIS ON THE DETERIORATION MECHANISM OF LEAD-ACID BATTERIES
    Hirano, Hiroki
    Kimura, Takayuki
    Sumiya, Keiji
    10TH INTERNATIONAL CONFERENCE ON LEAD-ACID BATTERIES (LABAT'2017), 2017, : 107 - 110
  • [4] Testing, dissection and analysis of lead-acid batteries
    Hammersley, VL
    Holloway, KL
    ELEVENTH ANNUAL BATTERY CONFERENCE ON APPLICATIONS AND ADVANCES, 1996, : 97 - 99
  • [5] Method and device for lead-acid batteries operating under critical applications
    Shirov, Boris
    Naydenov, Vesselin
    10TH INTERNATIONAL CONFERENCE ON LEAD-ACID BATTERIES (LABAT'2017), 2017, : 115 - 115
  • [6] Review on the research of failure modes and mechanism for lead-acid batteries
    Yang, Jun
    Hu, Chen
    Wang, Hao
    Yang, Kai
    Liu, Jing Bing
    Yan, Hui
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2017, 41 (03) : 336 - 352
  • [7] Prospects for lead-acid batteries
    Wrobel, Justyna
    Wrobel, Kamil
    Lach, Jakub
    Czerwinski, Andrzej
    PRZEMYSL CHEMICZNY, 2020, 99 (03): : 467 - 471
  • [8] Sulfation in lead-acid batteries
    Catherino, HA
    Feres, FF
    Trinidad, F
    JOURNAL OF POWER SOURCES, 2004, 129 (01) : 113 - 120
  • [9] DRY LEAD-ACID BATTERIES
    TIEGEL, EG
    METALL, 1969, 23 (01): : 41 - &
  • [10] LEAD-ACID STATIONARY BATTERIES
    THOMAS, UB
    JOURNAL OF THE ELECTROCHEMICAL SOCIETY, 1952, 99 (09) : C238 - C241