Short circuit analysis of a fault-tolerant current-limiting high temperature superconducting transformer in a power system in presence of distributed generations

被引:1
|
作者
Sadeghi, Alireza [1 ]
Bonab, Shahin Alipour [1 ]
Song, Wenjuan [1 ]
Yazdani-Asrami, Mohammad [1 ]
机构
[1] Univ Glasgow, James Watt Sch Engn, Autonomous Syst & Connect Div, Prop Electrificat & Superconduct Grp, Glasgow City G12 8QQ, Scotland
来源
SUPERCONDUCTIVITY | 2024年 / 9卷
关键词
Fault Energy; Heat dissipation; Heat transfer; Insulation; Recovery Time; Temperature rise; AC LOSS; FLUX DIVERTORS; HTS;
D O I
10.1016/j.supcon.2024.100085
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Power transformers are key elements for the safe and reliable delivery of electrical energy generated by renewable energy resources to consumers via transmission lines. Fault -tolerant current-limiting High Temperature Superconducting (FTCL HTS) transformers are type of superconducting transformers that tolerate fault for seconds and limit the fault current without the threat of burnout or delamination of tapes and deformation of windings. In this paper, the fault performance of a FTCL HTS transformer in a standard IEEE power system is investigated. The studied transformer is a 50 MVA 132 kV/13.8 kV transformer where both windings are made up of HTS tapes. The understudied power system consists of two microgrids with distributed generators. Part of the power in microgrids is supplied by the upstream grid which is connected to the microgrids through the HTS transformers. Two fault scenarios have been considered in this power system, in each one of these scenarios, a fault happens in one of the microgrids. Two considered fault scenarios have an approximate fault current of 18x to 23x of the rated current in the secondary windings. Results showed that insulated windings in FTCL HTS transformers could substantially reduce the peak temperature of the HTS windings, compared to bare windings. Afterwards, post -fault loading is imposed on the HTS windings, to observe their performance against the current increase after fault clearance. In this case, for the first scenario of the faults, the FTCL HTS transformer could tolerate 192% of post -fault overloading, while this number for the second fault scenario is 170%. Finally, the impact of post -fault loading on the full recovery time was discussed.
引用
收藏
页数:13
相关论文
共 50 条
  • [1] Multistage AC transmission expansion planning including fault current-limiting high-temperature superconducting cables and multiple distributed generations to improve short-circuit level and grid-scale flexibility
    Shivaie, Mojtaba
    Artis, Reza
    Padmanaban, Sanjeevikumar
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2024, 18 (09) : 1947 - 1969
  • [2] Short-circuit fault current-limiting characteristics of a resistive-type superconducting fault current limiter in DC grids
    Xiang, Bin
    Gao, Lei
    Liu, Zhiyuan
    Geng, Yingsan
    Wang, Jianhua
    SUPERCONDUCTOR SCIENCE & TECHNOLOGY, 2020, 33 (02):
  • [3] Role of Insulation Materials and Cryogenic Coolants on Fault Performance of MW-Scale Fault-Tolerant Current-Limiting Superconducting Transformers
    Yazdani-Asrami, Mohammad
    Sadeghi, Alireza
    Seyyedbarzegar, Seyyedmeysam
    Song, Wenjuan
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2023, 33 (01)
  • [4] Characterization Modelling and Current Limiting Performance Analysis of High Temperature Superconducting Transformer Under the Fault Current Impact in Power Grid
    Zhu J.
    Zhang H.
    Yang Y.
    Chen P.
    Qiu M.
    Fu S.
    Zheng X.
    Fang J.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2019, 39 (14): : 4292 - 4300
  • [5] Line fault test of model power system with three-phase superconducting fault current-limiting reactors
    Kado, Hiroyuki
    Uriu, Yoshihisa
    Ishigooka, Takeshi
    Electrical Engineering in Japan (English translation of Denki Gakkai Ronbunshi), 1992, 112 (04): : 85 - 90
  • [6] Short circuit fault-tolerant LCC-S wireless power transfer system
    Han, Xuelong
    Hou, Yinyin
    Jiang, Chundi
    Ye, Yinzhong
    JOURNAL OF POWER ELECTRONICS, 2022, 22 (02) : 187 - 197
  • [7] A novel current-limiting circuit based on resistive-type SFCL for fault in DC power system
    Shu, Ji
    Wang, Shunliang
    Liu, Tianqi
    Jiao, Ning
    Wang, Yanbo
    MICROELECTRONICS RELIABILITY, 2018, 88-90 : 1201 - 1205
  • [8] Short circuit fault-tolerant LCC-S wireless power transfer system
    Xuelong Han
    Yinyin Hou
    Chundi Jiang
    Yinzhong Ye
    Journal of Power Electronics, 2022, 22 : 187 - 197
  • [9] High-temperature superconducting power transformers with fault current limiting properties
    Sissimatos, E
    Oswald, BR
    PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2002, 372 (PART 3): : 1698 - 1701
  • [10] Superconductor-Circuit-Temperature Coupled Simulation of a Fault-Tolerant Boost Converter Employing Superconducting Fault Current Limiter
    Xie, Qi
    Chen, Xiao Yuan
    Chen, Yu
    Gou, Hua Yu
    Jiang, Shan
    Xu, Hao Yu
    Hu, Sheng Yuan
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2021, 31 (08)