Voltage and frequency regulation in smart grids via a unique Fuzzy PIDD2 controller optimized by Gradient-Based Optimization algorithm

被引:10
|
作者
AboRas, Kareem M. [1 ]
Ragab, Muhammad [1 ]
Shouran, Mokhtar [2 ]
Alghamdi, Sultan [3 ,4 ]
Kotb, Hossam [1 ,2 ]
机构
[1] Alexandria Univ, Fac Engn, Dept Elect Power & Machines, Alexandria 21544, Egypt
[2] Cardiff Univ, Wolfson Ctr Magnet, Sch Engn, Cardiff CF24 3AA, Wales
[3] King Abdulaziz Univ, Fac Engn, Dept Elect & Comp Engn, Jeddah, Saudi Arabia
[4] King Abdulaziz Univ, Ctr Res Excellence Renewable Energy & Power Syst, Jeddah, Saudi Arabia
关键词
Combined LFC-AVR; PIDD2; controller; Fuzzy logic control; Renewable energy sources GBO algorithm; Two-area system; ITAE; OPTIMUM DESIGN; AVR; LFC; SYSTEM; STABILITY; MODEL;
D O I
10.1016/j.egyr.2022.12.054
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper proposes a maiden intelligent controller design that consists of a Fuzzy Proportional- Integral-Derivative-Double Derivative (FPIDD2) controller whose parameters are fine-tuned using the Gradient-Based Optimization algorithm (GBO). The proposed FPIDD2 regulator is employed as a secondary regulator for stabilizing the combined voltage and frequency loops in a two-area interconnected power system. It has been shown that the GBO optimization algorithm outperforms other optimization strategies such as the Chimp Optimization Algorithm (ChOA), the Whale Optimization Algorithm (WOA), and the Gorilla Troops Optimization algorithm (GTO). The proposed FPIDD2 controller is tested in a conventional two-area power system. Then, the investigation is expanded to a two-area hybrid system, with each area comprising a mix of traditional (thermal, gas, and hydraulic power plants) and renewable generation units (wind and solar power). Additionally, the proposed controller takes into account system nonlinearities (such as generation rate limitations, governor deadband, and communication time delays), system uncertainties, and load/renewables fluctuations. In the two tested systems, the dynamic responses of each system demonstrate that FPIDD2 has a superior ability to attenuate the deviations in voltage and frequency in both areas of the system. In the studied conventional system, the proposed FPIDD2 controller is compared with a PID controller tuned by the Multi-Objective Non-Linear Threshold Accepting Algorithm (MONLTA), which has been presented in the literature, and a Fuzzy PID (FPID) controller tuned by GBO. In the investigated hybrid system, the suggested FPIDD2 regulator is compared to a GBO-tuned Integral Derivative-Tilted (ID-T) controller and FPID controller. As a fitness function (FF) for the GBO, the criteria of minimizing the integral time absolute error (ITAE) are applied. The results are presented in the form of MATLAB/SIMULINK time-domain simulations.(c) 2022 The Author(s). Published by Elsevier Ltd. This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).
引用
收藏
页码:1201 / 1235
页数:35
相关论文
共 18 条
  • [1] Optimal design of Fractional order PID controller based Automatic voltage regulator system using gradient-based optimization algorithm
    Altbawi S.M.A.
    Mokhtar A.S.B.
    Jumani T.A.
    Khan I.
    Hamadneh N.N.
    Khan A.
    Journal of King Saud University - Engineering Sciences, 2024, 36 (01) : 32 - 44
  • [2] Whale Optimization Algorithm Optimized Fuzzy-PID Plus PID Hybrid Controller for Frequency Regulation in Hybrid Power System
    Kumar A.
    Suhag S.
    Journal of The Institution of Engineers (India): Series B, 2022, 103 (02) : 633 - 648
  • [3] Robot Path Planning Based on Interval Type-2 Fuzzy Controller Optimized by an Improved Aquila Optimization Algorithm
    Li, Kun
    Zhang, Xiang
    Han, Ying
    IEEE ACCESS, 2023, 11 : 111655 - 111671
  • [4] Application of Interval Type-2 Fuzzy PID Controller for Frequency Regulation of AC Islanded Microgrid Using Modified Equilibrium Optimization Algorithm
    Khadanga, Rajendra Kumar
    Kumar, Amit
    Panda, Sidhartha
    ARABIAN JOURNAL FOR SCIENCE AND ENGINEERING, 2021, 46 (10) : 9831 - 9847
  • [5] Application of Interval Type-2 Fuzzy PID Controller for Frequency Regulation of AC Islanded Microgrid Using Modified Equilibrium Optimization Algorithm
    Rajendra Kumar Khadanga
    Amit Kumar
    Sidhartha Panda
    Arabian Journal for Science and Engineering, 2021, 46 : 9831 - 9847
  • [6] An improved moth swarm algorithm based fractional order type-2 fuzzy PID controller for frequency regulation of microgrid system
    Prusty, Umesh Chandra
    Nayak, Pratap Chandra
    Prusty, Ramesh Chandra
    Panda, Sidhartha
    ENERGY SOURCES PART A-RECOVERY UTILIZATION AND ENVIRONMENTAL EFFECTS, 2022,
  • [7] Chaotic Harris Hawks Optimization based type-2 Fractional Order Fuzzy PID controller for frequency regulation of power systems
    Sahoo, Dillip Kumar
    Sahu, Rabindra Kumar
    Panda, Sidhartha
    INTERNATIONAL JOURNAL OF AMBIENT ENERGY, 2020, : 3832 - 3844
  • [8] Chaotic Harris Hawks Optimization based type-2 Fractional Order Fuzzy PID controller for frequency regulation of power systems
    Sahoo, Dillip Kumar
    Sahu, Rabindra Kumar
    Panda, Sidhartha
    International Journal of Ambient Energy, 2022, 43 (01): : 3832 - 3844
  • [9] State-of-the-Art Frequency Control Strategy Based on an Optimal Fuzzy PI-FOPDFλ for SMES and UPFC Integrated Smart Grids Using Zebra Optimization Algorithm
    Ghadi, Yazeed Yasin
    Neamah, Nabeel Mohammed
    Hossam-Eldin, Ahmed A.
    Alqarni, Mohammed
    Aboras, Kareem M.
    IEEE ACCESS, 2023, 11 : 122893 - 122910
  • [10] Dual degree branched type-2 fuzzy controller optimized with a hybrid algorithm for frequency regulation in a triple-area power system integrated with renewable sources
    Kumari, Nisha
    Aryan, Pulakraj
    Raja, G. Lloyds
    Arya, Yogendra
    PROTECTION AND CONTROL OF MODERN POWER SYSTEMS, 2023, 8 (01)