关键词
Turbo-generator; stator internal short-circuit fault; generator protection method; instantaneous power oscillation ratio; DIFFERENTIAL PROTECTION; SYNCHRONOUS GENERATORS; WINDINGS; DIAGNOSIS; SYSTEM;
D O I
10.1109/TEC.2023.3237217
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
For large turbo-generators, the longitudinal differential protection can only reflect the stator internal inter-phase short-circuit fault, and cannot reflect the inter-turn short-circuit fault. The protection methods for inter-turn short-circuit faults have the problem of low sensitivity, such as the longitudinal zero-sequence voltage protection and the negative sequence component-based protection. Therefore, a stator internal short-circuit fault protection method for turbo-generator based on instantaneous power oscillation ratio (IPOR) is proposed in this paper. The instantaneous power variation of the generator before and after the fault is analyzed, and the IPOR is calculated by using the balanced power component and the oscillatory power component. Then, the method to judge whether the generator has an internal short-circuit fault based on the amplitude and phase of IPOR is proposed. The experimental results verify the effectiveness of the proposed protection method, which has a high sensitivity to the inter-turn short-circuit faults with a small turn difference. The protection is stable and does not malfunction during the system oscillation. In addition, the action time of the protection method does not exceed 1.5 power frequency cycles under various working conditions, which can meet the speed requirements of generator protection.
引用
收藏
页码:1903 / 1912
页数:10
相关论文
共 50 条
  • [1] Analysis on Torsional Stresses in Turbo-generator Shafts due to Two-Phase Short-Circuit Fault
    Gu, Yujiong
    Xu, Jing
    [J]. ADVANCED DESIGN AND MANUFACTURING TECHNOLOGY III, PTS 1-4, 2013, 397-400 : 427 - 430
  • [2] Fault diagnosis of excitation winding inter-turn short circuit of nuclear power half speed turbo-generator based on stator double coils
    Ma, Ming-Han
    Wu, Yu-Cai
    Li, Yong-Gang
    Wang, Luo
    [J]. Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2019, 23 (06): : 10 - 17
  • [3] Negative-sequence Component Analysis of an AP1000 Nuclear Turbo-generator in an Internal Short-circuit Condition
    Guo, Wu
    Ge, Bao-Jun
    Gao, Yun-Peng
    Li, Ming-Ze
    [J]. ELECTRIC POWER COMPONENTS AND SYSTEMS, 2015, 43 (06) : 633 - 643
  • [4] Fault diagnosis method based on wavelet neural network for power system turbo-generator
    Guangbin, Ding
    Peilin, Pang
    [J]. PROCEEDINGS OF THE 26TH CHINESE CONTROL CONFERENCE, VOL 6, 2007, : 259 - +
  • [5] Multifield Calculation and Analysis of Excitation Winding Interturn Short Circuit Fault in Turbo-Generator
    Ma, Minghan
    Li, Yonggang
    Wu, Yucai
    Dong, Chenchen
    [J]. ENERGIES, 2018, 11 (10)
  • [6] Study on dynamic response of torsional vibration of turbo-generator unit caused by short circuit fault
    He, Chengbing
    Chen, Dongchao
    Gu, Yujiong
    [J]. MACHINE DESIGN AND MANUFACTURING ENGINEERING, 2012, 566 : 248 - 252
  • [7] Effect of Internal Power-angle on Turbo-Generator Stator Vibration Characteristics under Eccentricity Faults
    Wan, Shuting
    He, Yuling
    Dou, Longjiang
    Sheng, Xiaoling
    [J]. JOURNAL OF THE CHINESE SOCIETY OF MECHANICAL ENGINEERS, 2015, 36 (03): : 211 - 220
  • [8] Analysis on Steady-State Electromagnetic Characteristics and Online Monitoring Method of Stator Inter-Turn Short Circuit of Turbo-Generator
    He, Yu-Ling
    Wang, Fa-Lin
    Tang, Gui-Ji
    Ke, Meng-Qiang
    [J]. ELECTRIC POWER COMPONENTS AND SYSTEMS, 2017, 45 (02) : 198 - 210
  • [9] The summarization of generator stator internal short-circuit faults transient rules researches based on multi-loop analysis method
    Niu, TL
    Fan, B
    [J]. ISTM/2005: 6TH INTERNATIONAL SYMPOSIUM ON TEST AND MEASUREMENT, VOLS 1-9, CONFERENCE PROCEEDINGS, 2005, : 8589 - 8592
  • [10] A Fault Equivalent Network Based Method for Calculating the Doubly Fed Wind Power Generator Short-circuit Currents
    Ma, Jing
    Huang, Tianyi
    Liu, Chang
    Sun, Lvyi
    Thorp, James S.
    [J]. ELECTRIC POWER COMPONENTS AND SYSTEMS, 2015, 43 (18) : 2069 - 2081