Experimental Study of Thermoelectric Heat Pump Water Heater with Exhaust Heat Recovery from Kitchens

被引:3
|
作者
LIU Zhong-bing
机构
基金
国家高技术研究发展计划(863计划);
关键词
thermoelectric heat pump; kitchens exhaust; water heater; coefficient of performance;
D O I
暂无
中图分类号
TU822 [热水供应设备];
学科分类号
0813 ;
摘要
A new kind of thermoelectric heat pump water heater for kitchens exhaust heat recovery was presented,and its performances were investigated under different operating voltages.The experiment results show that the coefficient of performance decreases and the temperature difference between the hot and cold sides becomes larger with the increase of the operating voltage,but the heating time becomes short.The higher the temperature of water,the greater the temperature difference between the hot and cold sides,leading to a smaller coefficient of performance.Under an exhaust temperature of 36 ℃,the coefficient of performance decreases from 1.66 to 1.22 when the temperature of water increases from 28 ℃ to 46 ℃ with operating voltage 16 V.Performance tests illustrate that,compared with the conventional electrical water heaters,the new kind of thermoelectric heat pump water heater is more coefficient.
引用
收藏
页码:131 / 135
页数:5
相关论文
共 1 条
  • [1] Experimental performance of a ceiling-type free convected thermoelectric air conditioner[J] . C. Lertsatitthanakorn,J. Hirunlabh,J. Khedari,M. Daguenet.International Journal of Ambient Energy . 2002 (2)