STATCOM and DFIG Reactive Power Management Strategy for LVRT Capability Enhancement Under Asymmetrical Grid Faults

被引:0
|
作者
Sayahi, Kamel [1 ]
Bouallegue, Belgacem [2 ]
Baazouzi, Mansour [1 ]
Bacha, Faouzi [3 ]
机构
[1] Univ Carthage, Dept Elect Engn, Comp Lab Ind Syst, INSAT, Carthage, Tunisia
[2] King Khalid Univ, Coll Comp Sci, Dept Comp Engn, Abha 61421, Saudi Arabia
[3] Univ Tunis, Dept Elect Engn, Tunis, Tunisia
关键词
doubly fed induction generator; low-voltage ride through; positive and negative sequences; synchronous static compensator; wind energy conversion system; STABILITY;
D O I
10.1155/er/7613713
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In the trajectory of carbon dioxide (CO2) neutrality, wind and solar energies will be the key for the energy transition in the electricity sector; however, a massive integration of solar and wind farms into the electricity grid by 2050 will be carried out. For this end, powers control and powers management of these two renewable energies have taken the attention of several researchers since the last decades. This article presents a reactive energy management strategy for a power grid linked to a wind farm utilizing doubly fed induction generators (DFIG) and enhanced by a static reactive power compensator (STATCOM). This management strategy improves an electrical grid capability in the event of a low-voltage ride through (LVRT) and aims to optimize the sizing of the STATCOM to be installed alongside the wind farm. The proposed oriented voltage control strategy (VOC) for the grid-side converter and STATCOM facilitates effective reactive current injection into the grid during symmetrical faults with significant voltage sags. A maximum power point tracking (MPPT) approach combined with stator flux-oriented control (FOC) applied to the rotor side converter enables effective control of the DFIG during an asymmetrical fault. Breaking down currents and voltages into positive and negative sequences expressed in the synchronous frame enhances DFIG and STATCOM control during grid voltage asymmetrical faults. The control algorithms are validated by simulation results using MATLAB-SIMULINK.
引用
收藏
页数:22
相关论文
共 50 条
  • [1] LVRT Capability of DFIG-Based WECS Under Asymmetrical Grid Fault Condition
    Geng, Hua
    Liu, Cong
    Yang, Geng
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (06) : 2495 - 2509
  • [2] Enhancement of DFIG Operation Using a STATCOM Under a Voltage Grid Faults
    Kamel, Sayahi
    Mansour, Baazouzi
    Faouzi, Bacha
    2022 8TH INTERNATIONAL CONFERENCE ON CONTROL, DECISION AND INFORMATION TECHNOLOGIES (CODIT'22), 2022, : 1550 - 1555
  • [3] Improved DFIG Capability during Asymmetrical Grid Faults
    Zhou, Dao
    Blaabjerg, Frede
    IECON 2015 - 41ST ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2015, : 1152 - 1157
  • [4] Enhancement of LVRT Capability in DFIG-Based Wind Turbines with STATCOM and Supercapacitor
    Dosoglu, M. Kenan
    SUSTAINABILITY, 2023, 15 (03)
  • [5] Active Power Enhancement Control Strategy of Grid-Forming Inverters Under Asymmetrical Grid Faults
    Zhang, Han
    Liu, Rui
    Xue, Cheng
    Li, Yunwei
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2024, 39 (01) : 1447 - 1459
  • [6] A New Reactive Power Management Strategy to Enhance the Behavior of the Wind Turbine Generator Driven a DFIG Under Grid Faults
    Belmokhtar, Karim
    Ibrahim, Hussein
    2015 IEEE ELECTRICAL POWER AND ENERGY CONFERENCE (EPEC), 2015, : 16 - 21
  • [7] Adaptive deactivating control strategy of Crowbar for LVRT capability enhancement of DFIG
    Jiang H.
    Zhou T.
    Jia Y.
    Chen J.
    Zhang C.
    Zhou Z.
    Xue J.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2018, 38 (09): : 93 - 98
  • [8] Capability of DFIG WTS to Ride through Recurring Asymmetrical Grid Faults
    Chen, Wenjie
    Blaabjerg, Frede
    Chen, Min
    Xu, Dehong
    2014 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2014, : 1827 - 1834
  • [9] Improved DFIG Control Strategy under Three-Phase Asymmetrical Grid Faults
    Song, Yipeng
    Zhou, Dao
    Blaabjerg, Frede
    2018 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2018, : 5515 - 5520
  • [10] Advanced Reactive Power Control Strategy for Better LVRT Capability for DFIG-based Wind Farm
    Gatavi, Ehsan
    Hellany, Ali
    Nagrial, Mahmood
    Rizk, Jamal
    2019 IEEE INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING AND 2019 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS EUROPE (EEEIC / I&CPS EUROPE), 2019,