Experimental and numerical investigation on the performance of a closed-wet cooling tower (CWCT) integrated into the underground exhaust air channel

被引:0
|
作者
Zhou, Xu [1 ]
Cao, Xiaoling [1 ]
Wang, Dongxu [1 ]
Wu, Lang [1 ]
Yuan, Yanping [1 ]
Huang, Lin [2 ]
Ma, Jiangyan [2 ]
机构
[1] Southwest Jiaotong Univ, Sch Mech Engn, 111,Sect 1,North Second Ring Rd, CN -610031 Chengdu, Peoples R China
[2] China Railway First Survey & Design Inst Grp Co Lt, Xian, Peoples R China
基金
中国国家自然科学基金;
关键词
Closed-wet cooling tower; Underground building; Underground air channel; Heat and mass transfer; Cooling capacity; COMPREHENSIVE DESIGN; EVAPORATIVE COOLERS; FLOW; SIMULATION; CONDENSERS;
D O I
10.1016/j.applthermaleng.2025.126368
中图分类号
O414.1 [热力学];
学科分类号
摘要
A closed-wet cooling tower (CWCT) integrated into an underground exhaust air channel is proposed in this paper. This design aims to harness the cooling capacity of exhaust air from underground buildings, thereby conserving space and enhancing overall space utilization in underground space. To elucidate the fundamental thermal characteristics of the CWCT, a numerical method was developed using COMSOL Multiphysics software to predict the heat and mass transfer processes within the tower. The reliability of this method was validated through experimental testing and also corroborated by two existing studies in the literature. Compared to conventional closed-wet cooling towers (CWCTs), the cooling performance of the CWCT is not significantly affected by the heat dissipation from nearby rocks. However, it demonstrates greater thermal efficiency than conventional ones. The thermal efficiency can be enhanced by adjusting the operating conditions, such as increasing the flow rate and inlet temperature of the cooling water, as well as the water spray density. However, it is important to note that the cooling efficiency only improves with an increase in water spray density. The sensitive analysis shows that the thermal efficiency and heat exchange capacity are most affected by water spray density, while the cooling efficiency is more affected by the cooling water mass flow rate. Therefore, adjusting the spray density might be the most recommended method for enhancing thermal performance. Under the current calculation conditions, adjusting the spray density can achieve a thermal efficiency of 30.77 % and a cooling efficiency of 48.57 %. Additionally, it can provide approximately 22.7 % of the cooling demand for the case building when the water spray density is set at 2.924 kg/(m2 & sdot;s). Moreover, connecting multiple heat exchanger units can enhance thermal efficiency while simultaneously reducing cooling efficiency. Under the current calculation conditions, it is advisable to connect two units in series within the air channel. The heat exchange capacity can reach 14.8 kW, with a cooling efficiency of 32.2 %, thereby meeting more than 29 % of the cooling demand for the case building.
引用
收藏
页数:20
相关论文
共 31 条
  • [1] Performance prediction of a prototype closed-wet cooling tower
    Gan, G
    Riffat, SB
    Shao, L
    JOURNAL OF THE INSTITUTE OF ENERGY, 2000, 73 (495): : 106 - 113
  • [2] Thermodynamic Investigation on the Performance of Closed Wet Cooling Tower
    Fang, Jiamei
    Zhao, Xuhui
    Zhang, Lin
    Bu, Shi
    Yu, Zhikang
    Xu, Weigang
    Hu, Yiyang
    Shan, Yanfei
    Li, Yong
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2022, 14 (03)
  • [3] Experimental investigation of the performance characteristics of a counterflow wet cooling tower
    Lemouari, M.
    Boumaza, M.
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2010, 49 (10) : 2049 - 2056
  • [4] Experimental Study on Performance of a Closed Wet Cooling Tower for Air Wet-Bulb Temperature near 0°C
    ZHOU Yasu
    ZHANG Pan
    ZHAO Jingde
    YANG Honghai
    BAI Yufeng
    JournalofThermalScience, 2019, 28 (05) : 1015 - 1023
  • [5] Experimental Study on Performance of a Closed Wet Cooling Tower for Air Wet-Bulb Temperature near 0°C
    Zhou Yasu
    Zhang Pan
    Zhao Jingde
    Yang Honghai
    Bai Yufeng
    JOURNAL OF THERMAL SCIENCE, 2019, 28 (05) : 1015 - 1023
  • [6] Experimental Study on Performance of a Closed Wet Cooling Tower for Air Wet-Bulb Temperature near 0°C
    Yasu Zhou
    Pan Zhang
    Jingde Zhao
    Honghai Yang
    Yufeng Bai
    Journal of Thermal Science, 2019, 28 : 1015 - 1023
  • [7] Experimental and numerical analysis of a cross-flow closed wet cooling tower
    Jiang, Jing-Jing
    Liu, Xiao-Hua
    Jiang, Yi
    APPLIED THERMAL ENGINEERING, 2013, 61 (02) : 678 - 689
  • [8] Theoretical Investigation on Thermal Performance of New Structure Closed Wet Cooling Tower
    Zhou, Yasu
    Zhu, Xun
    Ding, Xiao
    HEAT TRANSFER ENGINEERING, 2018, 39 (05) : 460 - 472
  • [9] Experimental and computational analysis of thermal performance of the oval tube closed wet cooling tower
    Zheng, Wei-Ye
    Zhu, Dong-Sheng
    Song, Jin
    Zeng, Li-Ding
    Zhou, Hong-jian
    APPLIED THERMAL ENGINEERING, 2012, 35 : 233 - 239
  • [10] EXPERIMENTAL INVESTIGATION OF THE THERMAL PERFORMANCE OF WET COOLING TOWER WITH SPLASH FILLS PACKING
    Ahmed, Shaymaa A.
    Aljaberi, Forat Yasir
    Makki, Hasan F.
    THERMAL SCIENCE, 2022, 26 (02): : 1603 - 1613