Stator electromagnetic force calculation and strength analysis of superconducting ultra high voltage synchronous condenser under multi-operating conditions

被引:0
|
作者
Xiao, Shiyong [1 ]
Zhang, Jiale [1 ]
Ge, Baojun [2 ]
Zhang, Jiancheng [3 ]
机构
[1] School of Electrical Engineering, Northeast Electric Power University, Jilin,132012, China
[2] School of Electrical and Electrical Engineering, Harbin University of Science and Technology, Harbin,150080, China
[3] State Grid Zhejiang Electric Power Research Institute, Hangzhou,310014, China
关键词
Condensers (liquefiers) - Electric current collection - Galvanomagnetic effects - HVDC power transmission - Machine windings - Magnetic leakage - Magnetic levitation - Static Var compensators - Superconducting cables - Superconducting electric machinery - Surface discharges - Transformer magnetic circuits - Transformer windings;
D O I
10.15938/j.emc.2024.10.004
中图分类号
学科分类号
摘要
Superconducting condenser adopts a new structure of high voltage stator with non-magnetic teeth of cable windings (referred to as superconducting ultra high voltage condenser), which can realize the direct connection between the condenser and the power grid. For the superconducting ultra high voltage condenser, the stator adopts a non-magnetic teeth structure, which leads to the increase of teeth reluctance, the increase of slot leakage, the uneven force on both sides of the stator teeth wall, and the tangential Lorentz force of the winding of the condenser is increased. The field-circuit coupled mathematical model of superconducting ultra high voltage condenser without step up transformer directly connected to power grid was established. Based on Maxwell stress method and Lorentz force principle, the electromagnetic force on stator teeth wall under four operating conditions of leading and lagging power factor operating and short time deep leading and lagging power factor operating was calculated, and the variation of electromagnetic force on both sides of the teeth wall with time and space were given. Using the calculated electromagnetic force as the load, the strength of stator teeth under different operating conditions was calculated, and the deformation size and stress distribution of the stator teeth were obtained. The results show that the non-magnetic stator teeth will not break when the superconducting ultra high voltage synchronous condenser operates under various operating conditions. The research provides a theoretical basis for using non-magnetic stator teeth and ultra high voltage winding structure for superconducting condenser. © 2024 Editorial Department of Electric Machines and Control. All rights reserved.
引用
收藏
页码:34 / 45
相关论文
共 22 条
  • [1] Probabilistic characteristic calculation of generator variables under multi-operating conditions
    Hu, Jinlei
    Zhang, Yao
    Guo, Li
    Xie, Huifan
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2007, 31 (11): : 39 - 43
  • [2] Discrete Stress-strength Interference Model of Reliability Analysis under Multi-operating Conditions
    An Zongwen
    Huang Hongzhong
    Wang Zhonglai
    Zhang Xiaoling
    Wang Guibao
    CHINESE JOURNAL OF MECHANICAL ENGINEERING, 2010, 23 (03) : 398 - 402
  • [4] Analysis of Electromagnetic Characteristics of Synchronous Condenser Under Stator Inter-turn Short Circuit Fault
    Ren, Zhangao
    Wang, Cong
    Ye, Liwen
    Hu, Jing
    Liu, Yun
    Zhou, Weihua
    2018 21ST INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS), 2018, : 2638 - 2642
  • [5] Calculation of Rotor Dynamic Electromagnetic Force of Synchronous Generator under the Stator Winding Interturn Short Circuit Fault
    Xiao S.
    Ge B.
    Tao D.
    Liu Z.
    Ge, Baojun (gebj@hrbust.edu.cn), 2018, China Machine Press (33): : 2956 - 2962
  • [6] Calculation of post-disturbance initial value for probabilistic transient stability analysis based on multi-operating conditions
    Hu, Jinlei
    Zhang, Yao
    Chen, Yanqiu
    Hou, Guanji
    Dianli Zidonghua Shebei / Electric Power Automation Equipment, 2008, 28 (11): : 17 - 21
  • [7] Calculation of Electromagnetic Force Waves and Analysis of Stator Vibration Characteristics of Surface Mount Permanent Magnet Synchronous Motor
    Xing Z.
    Wang X.
    Zhao W.
    Ma G.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (14): : 5004 - 5013
  • [8] Experimental analysis on the collaborative operation of fuel cell and adsorption chiller composite system under multi-operating conditions
    Zhao, Junjie
    Cai, Shanshan
    Luo, Xiaobing
    Tu, Zhengkai
    Chan, Siew Hwa
    ENERGY CONVERSION AND MANAGEMENT, 2023, 294
  • [9] Multi-Mode Coordinated Control Strategy for DC Receiving Converter Station with Synchronous Condenser under Full Operating Conditions
    Li H.
    Wang Z.
    Zhou T.
    Mao W.
    Wang X.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2020, 35 (17): : 3678 - 3690
  • [10] Analysis of calculation of fuel rods for strength under transient and steady-state operating conditions
    Lys, Stepan
    Kanyuka, Alexandr
    NUCLEAR MATERIALS AND ENERGY, 2024, 38