Distributed optimal control of parallel water pumps in heat exchange station

被引:0
|
作者
Zhao A.-J. [1 ]
Xi J.-T. [2 ]
Jing J. [3 ]
Zhao X. [2 ]
机构
[1] School of Building Services Science and Engineering, Xi’an University of Architecture and Technology, Shaanxi, Xi’an
[2] School of Information and Control Engineering, Xi’an University of Architecture and Technology, Shaanxi, Xi’an
[3] China Northwest Architecture Design And Research Institute Co. Ltd, Shaanxi, Xi’an
关键词
distributed control system; fruit fly optimization algorithm; heat exchange station; load optimization distribution; parallel water pump;
D O I
10.7641/CTA.2012.11081
中图分类号
学科分类号
摘要
Aiming at the problem that the optimization algorithm of parallel circulating pump in existing heat exchange station has insufficient control adaptability under centralized structure, an improved distributed parallel circulating pump optimization algorithm was proposed. Firstly, a distributed control system of parallel circulating pumps was established, and the mathematical model of the optimization problem was described, and the adaptive nonlinear factor was introduced into the objective function. Then, an improved distributed fruit fly optimization algorithm was designed, in which the controller of each water pump can complete the optimization of parallel circulating pumps only by interacting with adjacent controllers. In the olfactory search stage, the sinusoidal cosine strategy was used to replace the random strategy given individual distance and direction. Finally, the algorithm was simulated and verified by different parallel circulating pump systems in two actual heat exchange stations, and the performance was analyzed based on the simulation results. The results show that compared with the traditional algorithm, the improved distributed fruit fly optimization algorithm can obtain a better control strategy, with the characteristics of fast convergence, good stability and strong robustness. The algorithm can be applied to the parallel pump optimization problems of different systems, and has scalability. Compared with the centralized algorithm in the actual engineering verification, the total power and computing time of the proposed algorithm are reduced by 5.47% and 29.90%, respectively. Therefore, it can meet the demand for optimal distribution of the heat load of parallel water pumps in actual heat exchange stations. © 2024 South China University of Technology. All rights reserved.
引用
收藏
页码:342 / 354
页数:12
相关论文
共 28 条
  • [1] WAIDE P, BRUNNER C U., Energy-efficiency policy opportunities for electric motor-driven systems, Iea Energy Papers, (2011)
  • [2] WANG S Q, XING J C, JIANG Z Y, Et al., Decentralized optimization algorithms for variable speed pumps operation based on local interaction game, Journal of Control Science and Engineering, (2018)
  • [3] MORALES L, AGUILAR J, GARSES-JIMENEZ A, Et al., Advanced fuzzy-logic-based context-driven control for HVAC management systems in buildings, IEEE Access, 8, pp. 16111-16126, (2020)
  • [4] SCIACOVELLI A, VERDAA V, GUELPA E., Pumping cost minimization in an existing district heating network, ASME International Mechanical Engineering Congress and Exposition, (2013)
  • [5] JAFARI-ASL J, AZIZYAN G, MONFARED S, Et al., An enhanced binary dragonfly algorithm based on a V-shaped transfer function for optimization of pump scheduling program in water supply systems (case study of Iran), Engineering Failure Analysis, 123, (2021)
  • [6] LIN Lichang, LIU Qingrong, RUAN Yingjun, Operation optimization of variable-speed parallel water pumps based on measured data, Science Technology and Engineering, 20, 30, pp. 12546-12551, (2020)
  • [7] WANG Tong, ZHU Duolin, ZHOU Xiao, Et al., Study on energy saving optimization of secondary water supply parallel pumps, Water & Wastewater Engineering, 57, 3, pp. 125-131, (2021)
  • [8] OLSZEWSKI P., Genetic optimization and experimental verification of complex parallel pumping station with centrifugal pumps, Applied Energy, 178, pp. 527-539, (2016)
  • [9] YANG T, YI L, WU J F, Et al., A survey of distributed optimization, Annual Reviews in Control, 47, pp. 278-305, (2019)
  • [10] YE Y, JING C., Global optimization of a central air-conditioning system using decomposition-coordination method, Energy and Buildings, 42, 5, pp. 570-583, (2010)