Waste heat utilization: Energy and economic benefits from multi-ejector chiller sub-cooling R744 supermarket refrigeration systems

被引:1
|
作者
Sengupta, Ayan [1 ]
Gullo, Paride [2 ]
Khorshidi, Vahid [3 ]
Dasgupta, Mani Sankar [1 ]
机构
[1] BITS Pilani, Dept Mech Engn, Smart Bldg Lab, Pilani 333031, Rajasthan, India
[2] Univ Southern Denmark, Inst Mech & Elect Engn, Alsion 2, DK-6400 Sonderborg, Denmark
[3] Danfoss AS, Nordborgvej 81, DK-6430 Nordborg, Denmark
关键词
Refrigeration; R744; Supermarket; Ejector chiller; Subcooling; Parallel compression; CO2; PERFORMANCE; CYCLE;
D O I
10.1016/j.energy.2024.133657
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study investigated the energy and economic benefits of a novel sub-cooling technique using a heat-driven multi-ejector chiller (HDEC) in R744 supermarket refrigeration systems. Two configurations were evaluated: a conventional booster system with HDEC (CBEC) and a parallel compression system with HDEC (PCEC). Among various natural refrigerants, R717 was identified as most suitable for the HDEC. Various multi-ejector combinations were examined to assess the potential for waste heat utilization and energy savings in the R744 refrigeration system. The CBEC system provided effective operation only at ambient temperatures above 31 degrees C, whereas the PCEC system was effective above 24 degrees C. Performance of the proposed configurations were compared with a conventional R744 booster system (CB) and a parallel compression system (PC) both devoid of HDEC. The PCEC system showed improvements in the coefficient-of-performance ranging from 4.2 % to 23.9 % at ambient temperatures between 28 degrees C and 40 degrees C compared to the baselines. In various warm-climatic zones, including India, the Middle East, Thailand, and the USA, energy savings of approximately 2.1 %-9.5 % were observed compared to the PC system. Economic analysis indicated a reasonable payback period of 2.1-2.7 years for the additional investment required for deploying the PCEC system in Phoenix.
引用
收藏
页数:17
相关论文
共 4 条
  • [1] Control optimization of R744 duo-temperature supermarket refrigeration system with multi-ejector
    Chen W.
    Yu M.
    Zhao H.
    Huagong Xuebao/CIESC Journal, 2020, 71 (07): : 3266 - 3277
  • [2] Transcritical R744 Supermarket Refrigeration System Integrated with a Heat-Driven Ejector Chiller
    Sengupta, Ayan
    Gullo, Paride
    Khorshidi, Vahid
    Dasgupta, Mani Sankar
    APPLIED SCIENCES-BASEL, 2025, 15 (06):
  • [3] Multi-ejector R744 booster refrigerating plant and air conditioning system integration-A theoretical evaluation of energy benefits for supermarket applications
    Gullo, Paride
    Hafner, Armin
    Cortella, Giovanni
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 75 : 164 - 176
  • [4] Energy, environmental, and economic analysis of novel R744/R290 cascade refrigeration systems designed for warm ambient conditions utilizing ejector
    Singha, Prosenjit
    Dasgupta, Mani Sankar
    Bhattacharyya, Souvik
    Hafner, Armin
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2024, 53