Measurements and vegetational impact of chemical drift from mechanical draft cooling towers

被引:0
|
作者
Rochow, J.J. [1 ]
机构
[1] Dept. Environm. Serv., Consumers Power Co., Jackson, Mich. 49201, United States
来源
Environmental Science and Technology | 1978年 / 12卷 / 13期
关键词
Calcium compounds - Environmental impact - Sulfur compounds - Water cooling towers;
D O I
暂无
中图分类号
学科分类号
摘要
Collection and analyses of precipitation prior to and after cooling tower operation at the Palisades Plant in southwestern Michigan resulted in high deposition rates of sulfate and calcium up to 92 m from the towers. Sulfate deposition rates during operation averaged up to 9. 0 g m** minus **2 month** minus **1 in areas within 50 m of the cooling towers and decreased to 0. 61 g m** minus **2 month** minus **1 between 700 and 1609 m. Calcium deposition rates during operation averaged up to 4. 5 g m** minus **2 month** minus **1 in areas within 50 m of the cooling towers and decreased to 0. 57 g m** minus **2 month** minus **1 between 700 and 1609 m. The high sulfate deposition rates were assumed to be responsible for severe vegetation damage within 92 m of the cooling towers.
引用
收藏
页码:1379 / 1383
相关论文