Examination of performance of water mist fire suppression systems under ventilation conditions

被引:0
|
作者
Liu, Z. [1 ]
Kim, A.K. [1 ]
Su, J.Z. [1 ]
机构
[1] Fire Risk Management, Institute for Res. in Construction, National Research Council of Canada, Ottawa, Ont. K1A 0R6, Canada
关键词
Fire fighting equipment - Fires - Flammability testing - Pressure effects - Ventilation;
D O I
10.1106/3ve8-wwt4-c3u4-feh9
中图分类号
学科分类号
摘要
This paper describes water mist fire suppression effectiveness under various ventilation conditions. The full-scale fire test series were conducted in an empty enclosure and in a simulated machinery space. Fire scenarios in the tests included small and large pool fires, spray fires and wood crib fires that were placed at different locations within the compartment. The ventilation conditions varied from no ventilation, natural ventilation to forced ventilation. A single-fluid/high pressure and a twin-fluid/low pressure water mist systems were used, respectively, in the tests. The test results showed that water mist suppression effectiveness was dependent on ventilation rates, fire size, type and location in the compartment as well as the characteristics of the water mist system used. During tests, both single- and twin-fluid water mist systems effectively extinguished fires under natural ventilation. Under forced ventilation, however, water mist fire suppression effectiveness was substantially reduced due to the strong mass exchange between the room and its surroundings.
引用
收藏
页码:164 / 193
相关论文
共 50 条
  • [1] Fire suppression performance of water mist under diverse desmoking and ventilation conditions
    Liu, Wei-Yi
    Chen, Chiun-Hsun
    Shu, Yi-Liang
    Chen, Wei-Ting
    Shu, Chi-Min
    PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2020, 133 : 230 - 242
  • [2] Fire suppression performance of water mist systems with additives
    Kim, AK
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL II, PT A AND B, 2000, 2 : 561 - 566
  • [3] Water mist fire suppression systems
    Dyer, J.
    Fire Engineers Journal, 1997, 57 (191):
  • [4] Experimental study of water mist fire suppression in tunnels under longitudinal ventilation
    Chen, Lvyi
    Zhu, Wei
    Cai, Xin
    Pan, Liwei
    Liao, Guangxuan
    BUILDING AND ENVIRONMENT, 2009, 44 (03) : 446 - 455
  • [5] Numerical analysis of how ventilation conditions impact compartment fire suppression by water mist
    Lee, Jaiho
    ANNALS OF NUCLEAR ENERGY, 2020, 136
  • [6] Fire suppression mechanism under the coupling effect of longitudinal ventilation and high pressure water mist
    Zhang, P.-H. (zhangpeihong@mail.neu.edu.cn), 2013, Northeast University (34):
  • [7] A Review of Additives for Water Mist Fire Suppression Systems
    Robinet, Antonin
    Chetehouna, Khaled
    FIRE TECHNOLOGY, 2024, 60 (05) : 2923 - 2961
  • [8] Influence of additives on the fire suppression performance of water mist
    Jiang, Juncheng, 1600, China University of Mining and Technology (43):
  • [9] Fire tests for water mist fire suppression systems in road tunnels
    Leucker, R.
    Leismann, F.
    UNDERGROUND - THE WAY TO THE FUTURE, 2013, : 366 - 375
  • [10] On the fire protection of a commercial kitchen using water mist fire suppression systems
    Yao, B.
    Chow, W.K.
    Architectural Science Review, 2002, 45 (04) : 317 - 322