Experimental and numerical study of airflow pattern and particle dispersion in a vertical ventilation duct

被引:0
|
作者
Phuong, Nguyen Lu [1 ]
Ito, Kazuhide [1 ]
机构
[1] Department of Energy and Environmental Engineering, Interdisciplinary Graduate School of Engineering Science, Kyushu University, 6-1 Kasuga-koen, Kasuga, Fukuoka 816-8580, Japan
基金
日本学术振兴会;
关键词
Air - Atmospheric movements - Turbulent flow - Ventilation - Deposition - Numerical models - Velocimeters - Flow visualization - Velocity measurement - Particle separators - Reynolds number;
D O I
暂无
中图分类号
学科分类号
摘要
A numerical simulation has been conducted to investigate the behavior of airflow and the dispersion of size-dependent particles in the ventilation duct. To examine the prediction accuracy for our numerical simulation, we compared computational fluid dynamics (CFD) results with particle image velocimetry (PIV) measurement data of airflow in an isothermal duct model. The low Reynolds number type k-e{open} turbulent model was selected for further calculation because its predictions were the most accurate in this study. A size-dependent particle transport approach, combining the Eulerian approach with low Reynolds k-e{open} turbulent model and Lagrangian particle trajectory tracking, was adopted to investigate the airflow pattern and particle removal efficiency in the ventilation duct. Two scenarios, one with and one without a baffle, were also compared to determine the effects on the particle transport mechanisms. We compared the effectiveness of particle removal as by using the simulated results, which showed that the fraction of coarse particles retained were higher than the fraction of fine particles retained. We found that a vertical duct with a baffle in a perfect sink condition on the wall surfaces increased particle deposition and decreased particle escape. Because of the two opposing particle removal mechanisms, i.e., deposition and escape, the impact of thermophoresis on particle retaining behavior was not as significant as that of airflow velocities. © 2012 Elsevier Ltd.
引用
收藏
页码:466 / 481
相关论文
共 50 条
  • [1] Experimental and numerical study of airflow pattern and particle dispersion in a vertical ventilation duct
    Phuong, N.L. (luphuongnguyen@kyudai.jp), 1600, Elsevier Ltd (59):
  • [2] Experimental and numerical study of airflow pattern and particle dispersion in a vertical ventilation duct
    Nguyen Lu Phuong
    Ito, Kazuhide
    BUILDING AND ENVIRONMENT, 2013, 59 : 466 - 481
  • [3] Experimental and numerical study of room airflow under stratum ventilation
    Lin, Zhang
    Tian, Lin
    Yao, Ting
    Wang, Qiuwang
    Chow, T. T.
    BUILDING AND ENVIRONMENT, 2011, 46 (01) : 235 - 244
  • [4] Numerical analysis of particle deposition in ventilation duct
    Zhao, B
    Chen, JJ
    BUILDING AND ENVIRONMENT, 2006, 41 (06) : 710 - 718
  • [5] Study on particle deposition in vertical square ventilation duct flows by different models
    Zhang, Jinping
    Li, Angui
    ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (05) : 1008 - 1018
  • [6] An experimental and numerical study of the particle dispersion in a ventilated room
    Gustiuc, M.
    Denes, T.
    El Hamdani, S.
    Limam, K.
    Colda, I.
    Air Pollution XIV, 2006, 86 : 365 - 374
  • [7] Experimental and numerical study of a duct/heat exchanger unit for building ventilation
    Manz, H
    Huber, H
    ENERGY AND BUILDINGS, 2000, 32 (02) : 189 - 196
  • [8] Study on the influence of ventilation parameters on the airflow temperature in excavation roadway and ventilation duct
    Wang, Jiuzhu
    Du, Cuifeng
    Wang, Yuan
    CASE STUDIES IN THERMAL ENGINEERING, 2021, 28
  • [9] A numerical investigation of vertical and horizontal laminar airflow ventilation in an operating room
    Sadrizadeh, Sasan
    Holmberg, Sture
    Tammelin, Ann
    BUILDING AND ENVIRONMENT, 2014, 82 : 517 - 525
  • [10] Experimental Investigation of Airflow Pattern of Fabric Air Dispersion System
    Wang, Xiaoli
    Li, Angui
    PROCEEDINGS OF THE 8TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, VOL 2: HVAC&R COMPONENT AND ENERGY SYSTEM, 2014, 262 : 429 - 438