For the oscillations risk assessment of the double-fed induction generator (DFIG) transmitted by the series-compensated grid, the negative-resistance effect of the DFIG is specially investigated in this paper. Firstly, based on the common control structure, the port-admittance model of the DFIG is established by analyzing its response characteristics to disturbances. On the basis, the equivalent rotor impedance of asynchronous generator is derived based on the equivalent electrical circuit analysis. Subsequently, the negative-resistance characteristics of the rotor circuit are further investigated and two characteristic indexes are defined to evaluate the oscillations risk. Finally, the accuracy of the port-admittance model and the effectiveness of the characteristic indexes are verified through the time-domain electro-magnetic transient simulation. From case studies, it indicates that the negative-resistance effect of the DFIG mainly depends on the rotor circuit of asynchronous generator. It is influenced by the rotating speed of the generator, the resistance of the rotor windings, and the controller parameters of the rotor-side converter. © 2022, Solar Energy Periodical Office Co., Ltd. All right reserved.
引用
收藏
页码:324 / 332
页数:8
相关论文
共 17 条
  • [1] WU B, LIANG Y Q, ZARGARI N, WU B, LIANG Y Q, Et al., Power conversion and control of wind energy systems, (2012)
  • [2] ADAMS J, PAPPU V A, DIXIT A., Ercot experience screening for sub-synchronous control interaction in the vicinity of series capacitor banks, 2012 IEEE Power and Energy Society General Meeting, (2012)
  • [3] LI M J, YU Z, XU T, Et al., Study of complex oscillation caused by renewable energy integration and its solution, Power system technology, 41, 4, pp. 1035-1042, (2017)
  • [4] DONG X L, TIAN X, ZHANG Y, Et al., Practical SSR incidence and influencing factor analysis of DFIG-based series-compensated transmission system in Guyuan farms, High voltage engineering, 43, 1, pp. 321-328, (2017)
  • [5] LIU B W, ZHANG X Y, CHANG X Q, Et al., Analysis of non-synchronous oscillation based on SWT and transient wave recorded data of PMU in wind farm integration area, Acta energiae solaris sinica, 41, 1, pp. 217-224, (2020)
  • [6] LI R, LU Y, LIU H L, Et al., Mechanism analysis on sub-synchronous oscillation caused by grid-integration of doubly-fed wind power generation system via series-compensation, Power system technology, 37, 11, pp. 3073-3079, (2013)
  • [7] HUANG Y, WANG X T, CHEN K M, Et al., SSI mechanism simulation validation and practical mitigation strategy of DFIG-based wind farms, Power system technology, 40, 8, pp. 2364-2369, (2016)
  • [8] OSTADI A, YAZDANI A, VARMA R K., Modeling and stability analysis of a DFIG-based wind-power generator interfaced with a series-compensated line, IEEE transactions on power delivery, 24, 3, pp. 1504-1514, (2009)
  • [9] ZHAO S Q, LI R, GAO B F, Et al., Modal analysis of doubly-fed induction generator integrated to compensated grid, High voltage engineering, 42, 10, pp. 3263-3273, (2016)
  • [10] MIAO Z., Impedance-model-based SSR analysis for type 3 wind generator and series-compensated network, IEEE transactions on energy conversion, 27, 4, pp. 984-991, (2012)