DOUBLE LOGARITHMIC DISTRIBUTION BASED SEISMIC FRAGILITY ANALYSIS OF PORCELAIN ELECTRICAL EQUIPMENT

被引:0
|
作者
Li J.-C. [1 ,2 ]
Shang Q.-X. [3 ]
Luo Q.-Y. [4 ]
Wang T. [1 ,2 ]
机构
[1] Key Laboratory of Earthquake Engineering and Engineering Vibration, Institute of Engineering Mechanics, China Earthquake Administration, Heilongjiang, Harbin
[2] Key Laboratory of Earthquake Disaster Mitigation, Ministry of Emergency Management, Heilongjiang, Harbin
[3] Department of Civil Engineering, Tsinghua University, Beijing
[4] China Academy of Building Research, Beijing
来源
关键词
double logarithmic distribution; electrical equipment; seismic fragility curve; substation system; system functionality;
D O I
10.6052/j.issn.1000-4750.2022.03.0261
中图分类号
学科分类号
摘要
Existing data on fragility functions of the 110 kV and 220 kV equipment are summarized and expressed by double logarithmic model to reflect the significant discreteness between different studies. The median capacities, randomness, and uncertainties of major 110 kV and 220 kV equipment are determined. Based on these parameters, the seismic performance, in particularly, the system functionality, of a 220 kV substation is assessed. The double logarithmic model is capable of reflecting the discreteness of the seismic fragilities of equipment in different studies, especially the uncertainties caused by modelling and analysis methods. The substation is found to be more vulnerable to earthquakes compared with individual pieces of equipment, indicating that the redundancy considered in current design should be improved. The substation’s median capacities are positively related to component median capacities, negatively related to component randomness and uncertainties. © 2024 Tsinghua University. All rights reserved.
引用
收藏
页码:125 / 136
页数:11
相关论文
共 57 条
  • [1] WEN Bo, NIU Ditao, ZHAO Peng, Review of substation seismic performance research, Earthquake Resistant Engineering and Retrofitting, 29, 6, pp. 73-77, (2007)
  • [2] CHENG Yongfeng, ZHU Quanjun, LU Zhicheng, Progress and development trend on seismic measures of electric power equipment in transformer substation, Power System Technology, 32, 22, pp. 84-89, (2008)
  • [3] YU Yongqing, LI Guangfan, LI Peng, Et al., Investigation and analysis of electric equipment damage in Sichuan power grid caused by Wenchuan earthquake, Power System Technology, 32, 11, pp. 5-10, (2008)
  • [4] The January 17, 1995 Kobe Earthquake: An EQE summary report, (1995)
  • [5] SCHIFF A J, TOGNAZZINI R, OSTROM D., Power systems after the Northridge earthquake: Emergency operations and changes in seismic equipment specifications, practice, and system configuration [J], Lifeline Earthquake Engineering, pp. 549-556, (1995)
  • [6] Preliminary investigation report on the seismic damage of the power facilities in the Wenchuan earthquake, (2008)
  • [7] SONG J H, KIUREGHIAN A D, SACKMAN J L., Seismic interaction in electrical substation equipment connected by non-linear rigid bus conductors [J], Earthquake Engineering & Structural Dynamics, 36, 2, (2007)
  • [8] CAO Meigen, ZHOU Fulin, TAN Ping, Et al., Earthquake response and isolation layer parameter effect of seismic isolation systems of transformers with bushings, Proceedings of the CSEE, 32, 13, pp. 166-174, (2012)
  • [9] XIE Qiang, MA Guoliang, ZHU Ruiyuan, Et al., Shaking table test research on earthquake response mechanism of a transformer-bushing system, Proceedings of the CSEE, 35, 21, pp. 5500-5510, (2015)
  • [10] MOUSTAFA M A, MOSALAM K., Finite element modeling and assessment of seismic response of electrical substations porcelain post insulators, Soil Dynamics and Earthquake Engineering, 150, pp. 106895:1-13, (2021)