Energy and environment analysis of R1234yf/R245fa cascade air source heat pump system with double ejectors

被引:1
|
作者
Li, Jing [1 ]
Li, Minxia [1 ]
Dang, Chaobin [2 ]
Wang, Qifan [1 ]
Dong, Liwei [1 ]
Liu, Xuetao [3 ]
机构
[1] Tianjin Univ, State Key Lab Engines, Tianjin 300350, Peoples R China
[2] Univ Fukui, Grad Sch Engn, Fukui 9108507, Japan
[3] Hisense Res & Dev R&D Ctr, Qingdao 266100, Peoples R China
关键词
Cascade heat pump; Ejector; Coefficient of performance; Economy; THEORETICAL-ANALYSIS; EXERGY; CYCLE;
D O I
10.1016/j.enconman.2024.119404
中图分类号
O414.1 [热力学];
学科分类号
摘要
For the purpose of improving the performance of the cascade heat pump system (CHPS) at low ambient temperature and promoting the process of global industrial decarbonization, single ejector cascade heat pump system (SECHPS) and double ejectors cascade heat pump system (DECHPS) are proposed in this research. The performance of nine refrigerant pairs (R1234yf/R245fa, R1234yf/R134a, R1234yf/R152a, R1234yf/R236ea, R1234yf/R1234ze, R32/R245fa, R125/R245fa, R152a/R245fa, R134a/R124fa) consisting of eight refrigerants (R1234yf, R125, R152a, R32, R134a, R245fa, R236ea, R1234ze) in the low temperature cycle (LTC) and high temperature cycle (HTC) in the three systems are compared initially. From the perspective of coefficient of performance (COP), safety and environmental characteristics, R1234yf is selected in the LTC, and R245fa is chosen in the HTC. The thermodynamic performance and economic efficiency are analyzed through thermodynamic and economic modeling, especially compared with the operating cost of the natural gas (NG) heating operation. Therefore, the COP of R1234yf/R245fa in the three systems is compared, and the results show that when evaporation temperature is -25 degrees C and the condensation temperature is 80 degrees C-100 degrees C, the COPs of SECHPS and DECHPS are increased by 3.87 %-4.68 % and 10.12 %-11.29 %, respectively. The pressure ratios of DECHPS in the LTC and HTC are decreased by 18.59 % and 17.23 %, respectively. The compressor power consumption of the SECHPS and DECHPS is lower than CHPS. Reducing the condensation temperature or increasing the evaporation temperature can reduce the amount of circulating working fluid charge and increase the COP of the system, and the ejection rate of LTC in the DECHPS is always higher than that of HTC. Further, when the heat supply is constant, the ejector system can reduce the electricity consumption of the system and the annual operating cost. Compared to the CHPS, the annual electricity consumption of SECHPS and DECHPS is reduced by 6.03 %-7.36 % and 13.34 %-15.83 %, respectively. The annual operating cost of DECHPS is reduced by 0.12 %-44.77 %. Moreover, the total equivalent warming impact (TEWI) of SECHPS decreased by 5.99 %- 7.30 %, and that of DECHPS decreased by 13.25 %-15.70 %, which can effectively reduce the impact on environmental emissions. The systems proposed in this paper have general applicability, and have more advantages in areas with hot summer and warm winter, high gas price and low or moderate electricity price, providing a theoretical reference for improving the energy efficiency of the HPS and realizing the goals of carbon peaking and carbon neutrality.
引用
收藏
页数:20
相关论文
共 50 条
  • [1] Investigation on the Performance of the Pump-Free Double Heat Source Ejector Refrigeration System with R1234yf
    YU Meihong
    ZHAO Hongxia
    WANG Xinli
    HAN Jitian
    LAI Yanhua
    JournalofThermalScience, 2022, 31 (05) : 1452 - 1464
  • [2] Investigation on the Performance of the Pump-Free Double Heat Source Ejector Refrigeration System with R1234yf
    Yu, Meihong
    Zhao, Hongxia
    Wang, Xinli
    Han, Jitian
    Lai, Yanhua
    JOURNAL OF THERMAL SCIENCE, 2022, 31 (05) : 1452 - 1464
  • [3] Investigation on the Performance of the Pump-Free Double Heat Source Ejector Refrigeration System with R1234yf
    Meihong Yu
    Hongxia Zhao
    Xinli Wang
    Jitian Han
    Yanhua Lai
    Journal of Thermal Science, 2022, 31 : 1452 - 1464
  • [4] Comparative Analysis of Heat Pump System with IHX Using R1234yf and R134a
    Santa, Robert
    PERIODICA POLYTECHNICA-MECHANICAL ENGINEERING, 2021, 65 (04): : 363 - 373
  • [5] Performance evaluation of an automotive air conditioning and heat pump system using R1234yf and R134a
    Aral, Mumin Celil
    Suhermanto, Mukhamad
    Hosoz, Murat
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2021, 27 (01) : 44 - 60
  • [6] Theoretical analysis and experimental research on R1234yf as alternative to R134a in a heat pump system
    Wang, Hongli
    Zhang, Shuaihua
    Li, Huasong
    Guo, Xiaoying
    ENVIRONMENTAL PROGRESS & SUSTAINABLE ENERGY, 2023, 42 (03)
  • [7] Experimental energy and exergy performance of an automotive heat pump using R1234yf
    Alpaslan Alkan
    Ahmet Kolip
    Murat Hosoz
    Journal of Thermal Analysis and Calorimetry, 2021, 146 : 787 - 799
  • [8] Experimental energy and exergy performance of an automotive heat pump using R1234yf
    Alkan, Alpaslan
    Kolip, Ahmet
    Hosoz, Murat
    JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2021, 146 (02) : 787 - 799
  • [9] Experimental Evaluation of an Automotive Heat Pump System with R1234yf as an Alternative to R134a
    Direk, Mehmet
    Yuksel, Fikret
    ARABIAN JOURNAL FOR SCIENCE AND ENGINEERING, 2020, 45 (02) : 719 - 728
  • [10] THEORETICAL STUDY OF HEAT PUMP SYSTEM USING R744/R1234YF AS REFRIGERANT
    Ju, Fujun
    Fan, Xiaowei
    Chen, Yaping
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2015, VOL 8B, 2016,