Start-up and shutdown control strategy for static synchronous series compensator

被引:0
|
作者
Huang R. [1 ]
Cao D. [1 ]
Dong Y. [1 ]
Pan L. [1 ]
Qiu D. [1 ]
Lu Y. [1 ]
机构
[1] Nanjing Nari-Relays Electric Co., Ltd., Nanjing
关键词
Self-excited; Start-up circuit; Static synchronous series compensator; Zero current; Zero voltage;
D O I
10.16081/j.issn.1006-6047.2019.07.017
中图分类号
学科分类号
摘要
The application and development of the SSSC(Static Synchronous Series Compensator) are restricted due to the difficulty of its start-up. A novel SSSC circuit with external charging circuit is proposed, whose charging state and normal operation state are designed as two different working modes. The start-up and shutdown control strategy for SSSC is analyzed in detail based on the proposed circuit, i.e. the bypass switch on the grid side is opened while its current is zero in start-up stage, and closed while its voltage is zero in shutdown stage. Therefore, the power of the grid is stable during the whole start-up and shutdown progress of SSSC. Finally, the proposed start-up and shutdown control strategy for SSSC is verified in the 220 kV Nanjing Western UPFC Project. © 2019, Electric Power Automation Equipment Press. All right reserved.
引用
收藏
页码:114 / 118
页数:4
相关论文
共 15 条
  • [1] Sen K., SSSC-static synchronous series compensator: theory, mode-ling, and applications, IEEE Transactions on Power Delivery, 13, 1, pp. 241-246, (1998)
  • [2] He D., Facts technology and new progress in the development of its controllers-TCPST, IPC(TCIPC) and SSSC, Automation of Electric Power Systems, 21, 6, pp. 1-6, (1997)
  • [3] Zhou J., Review of the applications of static synchronous series compensator in power system, Electrotechnical Application, 25, 4, (2006)
  • [4] Zhang F., Xu Z., Study on control and characteristics of static synchronous series compensator, Proceedings of the CSEE, 28, 19, pp. 75-80, (2008)
  • [5] Liu H., Jiang X., Xiao X., The simulation of SSSC based on cascaded multilevel inverter, Modern Electric Power, 23, 2, pp. 19-23, (2006)
  • [6] Zhang A., Zhang J., Jiang C., Constant-impedance model of static synchronous series compensator and its double closed loop control strategy, Power System Technology, 34, 3, pp. 106-111, (2010)
  • [7] Wu J., Jiang C., Zhang J., Et al., A novel static synchronous series compensator control strategy for improving the dynamic performance of power systems, Transactions of China Electrotechnical Society, 26, 12, pp. 156-161, (2011)
  • [8] Lu J., Qin J., Pan L., Et al., Study on architecture and configuration for control and protection system of Nanjing UPFC project, Jiangsu Electrical Engineering, 34, 6, pp. 1-5, (2015)
  • [9] Du Y., Zhu K., Jiang D., Et al., DC distribution network containing SSSC-FCL, Electric Power Automation Equipment, 34, 8, (2014)
  • [10] Ling F., Li J., Tian J., Et al., Optimization analysis of UPFC system structure for double-circuit lines, Automation of Electric Power Systems, 39, 21, pp. 113-119, (2015)