Hybrid heat-pump-driven liquid-desiccant system: Experimental performance analysis for residential air-conditioning applications

被引:0
|
作者
Lee, Jae-Hee [1 ]
Jeong, Jae-Weon [1 ]
机构
[1] Department of Architectural Engineering, College of Engineering, Hanyang University, 222 Wangsimni-Ro, Seongdong-Gu, Seoul,04763, Korea, Republic of
关键词
Air conditioning;
D O I
暂无
中图分类号
学科分类号
摘要
A compact heat-pump-driven liquid-desiccant air-conditioning unit for residential buildings is proposed and constructed to validate its energy and air-conditioning performance experimentally. By composing the system with one set of providing the decoupled control of annual sensible and latent loads, the proposed system would contribute to the residential applicability as a packaged multi-functional air-conditioning system. The proposed system consists of a liquid-desiccant dehumidifier to accommodate the latent load and a heat-pump to meet the sensible load of the conditioned zone. The heat-pump also simultaneously accommodates the desiccant-solution cooling and heating demands required in the operation of the liquid-desiccant system. The operating and energy performances of the proposed system for representative summer and winter modes are monitored through a full-size test mock-up in a laboratory. The measurement data reveals that the proposed system can consistently maintain the target supply-air temperature and humidity in each operation mode. In terms of energy efficiencies, the proposed system exhibits an energy efficiency ratio of 7.72 for the summer and a coefficient of performance of 2.51 for the winter operating conditions, which satisfy the approved minimum efficiency requirements. In conclusion, the proposed system has a great application potential for residences in terms of operating and energy performances. © 2021 Elsevier Ltd
引用
收藏
相关论文
共 50 条
  • [1] Hybrid heat-pump-driven liquid-desiccant system: Experimental performance analysis for residential air-conditioning applications
    Lee, Jae-Hee
    Jeong, Jae-Weon
    [J]. APPLIED THERMAL ENGINEERING, 2021, 195
  • [2] Inactivation of airborne microbial contaminants by a heat-pump-driven liquid-desiccant air-conditioning system
    Lee, Jae-Hee
    Bang, Jong-Il
    Sung, Minki
    Jeong, Jae-Weon
    [J]. JOURNAL OF BUILDING ENGINEERING, 2022, 50
  • [3] Multi-objective optimization for capacity matching and energy performance of heat-pump-driven liquid-desiccant air-conditioning system
    Lee, Jae-Hee
    Cheon, Seong-Yong
    Jeong, Jae-Weon
    [J]. APPLIED THERMAL ENGINEERING, 2023, 229
  • [4] Investigation of a compact hybrid liquid-desiccant air-conditioning system for return air dehumidification
    Guan, Bowen
    Liu, Xiaohua
    Zhang, Tao
    [J]. BUILDING AND ENVIRONMENT, 2021, 187
  • [5] Optimization of solution concentration in liquid desiccant air-conditioning system driven by heat pump
    Guan, Bowen
    Liu, Xiaohua
    Zhang, Tao
    [J]. ENERGY AND BUILDINGS, 2020, 225
  • [6] Simulation on a liquid-desiccant air conditioning system without pump
    Zhao, Wei
    Zhu, Ruiqi
    Kan, Yisong
    [J]. Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 2002, 36 (01): : 30 - 34
  • [7] Experimental study on passive-mixing strategy of a liquid-desiccant air-conditioning system
    Lee, Jae-Hee
    Jeong, Jae-Weon
    [J]. APPLIED THERMAL ENGINEERING, 2024, 243
  • [8] Dynamic model and response characteristics of liquid desiccant air-conditioning system driven by heat pump
    Guan, Bowen
    Liu, Xiaohua
    Zhang, Tao
    Wang, Andong
    [J]. BUILDING SIMULATION, 2021, 14 (06) : 1773 - 1784
  • [9] Dynamic model and response characteristics of liquid desiccant air-conditioning system driven by heat pump
    Bowen Guan
    Xiaohua Liu
    Tao Zhang
    Andong Wang
    [J]. Building Simulation, 2021, 14 : 1773 - 1784
  • [10] Performance analysis of a liquid desiccant and membrane contactor hybrid air-conditioning system
    Bergero, Stefano
    Chiari, Anna