Online Detection Method for Capacitor Voltage Transformer Measurement Error Adapted to Nonstationary Random Processes

被引:0
|
作者
Zhang, Zhu [1 ]
Lu, Heng [1 ]
Li, Binbin [2 ]
Qin, Shaorui [2 ]
Ding, Lijian [1 ]
机构
[1] Hefei Univ Technol, Sch Elect Engn & Automat, Hefei 230009, Peoples R China
[2] China & State Grid Anhui Elect Power Co, Elect Power Res Inst, Hefei 230601, Peoples R China
基金
中国国家自然科学基金;
关键词
Principal component analysis; Voltage measurement; Measurement errors; Data models; Measurement uncertainty; Kernel; Feature extraction; Accuracy; Transformers; Matrix decomposition; Capacitor voltage transformer (CVT); enhanced integrated principal component analysis (EIPCA); measurement error; modeling error; nonstationary random process; online detection;
D O I
10.1109/TIM.2024.3472842
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Capacitor voltage transformers (CVTs) are measurement devices widely used in high-voltage power grids, and the long-term stability of their measurement errors affects the safe operation of power systems. To address the problem of insufficient real-time periodic calibration using standard transformers, this article proposes an online detection method for CVT measurement error based on enhanced integrated principal component analysis (EIPCA). Considering that the secondary output voltage of CVTs is characterized by a nonstationary random distribution, the method combines the advantages of principal component analysis (PCA) and kernel principal component analysis (KPCA) to enhance its ability to process mixed linear and nonlinear data. It performs variational mode decomposition (VMD) of the linear residuals mapped in the cascade process to eliminate the modeling error caused by nonstationary data. Finally, the residual component characterizing the integrated error information of the CVT is separated from the primary voltage fluctuation, and the $T<^>{2}$ statistic is established as the index of measurement error detection. The experimental results show that the EIPCA-based online error detection method proposed in this article can effectively detect the 0.2-level error of the CVT, significantly improving detection performance compared with traditional PCA.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] Self-detection method for measurement error of capacitor voltage transformer considering conversion error
    Zhu, Zhang
    Heng, Lu
    Binbin, Li
    REVIEW OF SCIENTIFIC INSTRUMENTS, 2024, 95 (01):
  • [2] Harmonic voltage measurement error of the capacitor voltage transformer
    Le, Jian
    Zhang, Hao
    Gao, Chao
    Zhou, Qian
    PLOS ONE, 2018, 13 (11):
  • [3] An online detection method for capacitor voltage transformer with excessive measurement error based on multi-source heterogeneous data fusion
    Zhang, Yuxuan
    Zhang, Chuanji
    Li, Hongbin
    Chen, Qing
    MEASUREMENT, 2022, 187
  • [4] Research on the Capacitor Voltage Transformer Measurement Error under Harmonic Environment
    Yuan Zhiyuan
    Zhao Wei
    2013 CHINESE AUTOMATION CONGRESS (CAC), 2013, : 104 - 109
  • [5] Research on the Measurement Error of Capacitor Voltage Transformer under Various Insulation Characteristics
    Lin, Du
    Bin, Chen
    Chen Weigen
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [6] Online measurement of capacitor voltage transformer metering errors based on GRU and MTL
    Zhang, Wanli
    Shi, Ying
    Yu, Jicheng
    Yang, Bo
    Lin, Chaojun
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 221
  • [7] Research on adaptive state prediction method for the metering error of capacitor voltage transformer
    Zhu, Zhang
    Binbin, Li
    Jianyi, Xue
    Lijian, Ding
    REVIEW OF SCIENTIFIC INSTRUMENTS, 2023, 94 (08):
  • [8] Detecting measurement error drifts of a capacitor voltage transformer on line and its field application
    Zhang, Chuanji
    Li, Hongbin
    Yang, Jian
    Chen, Mianzhou
    Jiao, Yang
    MEASUREMENT SCIENCE AND TECHNOLOGY, 2019, 30 (10)
  • [9] Error Analysis of Capacitor Voltage Transformer in the Operation Environment
    Zhang Fuzhou
    Liu Kun
    Chen Xianshun
    Huang Jiapeng
    Luo Ruixi
    Liu Gang
    Li Yongsen
    Zhou Kai
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [10] Equivalent transformation based method for capacitor voltage transformer (CVT) transient error correction
    Xu, Ming
    Gao, Houlei
    Zou, Guibin
    Liu, Hongzheng
    Yang, Ronghua
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2011, 35 (01): : 71 - 76