Numerical analysis of rack-based data center cooling with rear door heat exchanger (RDHx): Interrelationship between thermal performance and energy efficiency

被引:1
|
作者
Cho, Jinkyun [1 ]
机构
[1] Hanbat Natl Univ, Dept Bldg & Plant Engn, Daejeon 34158, South Korea
基金
新加坡国家研究基金会;
关键词
Data center; IT power density; Rack-based cooling; RDHx; Rear door heat exchanger; CFD simulation; Energy modeling;
D O I
10.1016/j.csite.2024.105247
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study presents a comprehensive numerical analysis of thermal performance and energy efficiency, IT operating environment, and thermal performance of the RDHx system, a rack-based cooling solution for high-density IT power using air-cooled equipment. A 150 kW IT module and RDHx cooling system were designed and evaluated, and CFD numerical analysis confirmed that RDHx maintains a stable IT environment within ASHRAE standards at a supply air temperature of 24 degrees C. Additionally, the chilled water supply temperature for the secondary CDU can be increased to 14 degrees C, and for the primary chiller to 12 degrees C. A central chilled water system for a 30 MW reference data center was designed and analyzed, showing increased efficiency with a 12 degrees C supply temperature and varying condenser water return temperatures in winter, resulting in an annual PUEcooling range of 1.25-1.33, with an average of 1.27. The annual energy consumption distribution for rack-based cooling is approximately 46 % from chillers, 21 % from fans, and 33 % from pumps. These results provide crucial insights into data center cooling and support the application of the RDHx system in high-density data centers, with future validation involving a field mock-up test of a 150 kW IT module.
引用
收藏
页数:15
相关论文
共 26 条
  • [1] COMPARATIVE THERMAL AND ENERGY ANALYSIS OF A HYBRID COOLING DATA CENTER WITH REAR DOOR HEAT EXCHANGERS
    Gao, Tianyi
    Samadiani, Emad
    Sammakia, Bahgat
    Schmidt, Roger
    PROCEEDINGS OF THE ASME INTERNATIONAL TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC MICROSYSTEMS, 2013, VOL 2, 2014,
  • [2] REAR DOOR HEAT EXCHANGER COOLING PERFORMANCE IN TELECOMMUNICATION DATA CENTERS
    Mynampati, Venkata Naga Poornima
    Karajgikar, Saket
    Sheerah, Ibraheem
    Agonafer, Dereje
    Novotny, Shlomo
    Schmidt, Roger
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION 2010, VOL 4, 2012, : 417 - +
  • [3] An Exergy-Based Analysis of the Effects of Rear Door Heat Exchange Systems on Data Center Energy Efficiency
    Wemhoff, Aaron P.
    Ortega, Alfonso
    2014 IEEE INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS (ITHERM), 2014, : 1129 - 1136
  • [4] Thermal Performance and Energy Saving Analysis of Indoor Air-Water Heat Exchanger Based on Micro Heat Pipe Array for Data Center
    Jing, Heran
    Quan, Zhenhua
    Zhao, Yaohua
    Wang, Lincheng
    Ren, Ruyang
    Liu, Zichu
    ENERGIES, 2020, 13 (02)
  • [5] NUMERICAL STUDY OF LATENT HEAT THERMAL ENERGY STORAGE BASED ON AN INNOVATIVE HEXAGONAL HEAT EXCHANGER: PERFORMANCE EVALUATION
    Laasri, Imad Ait
    Elmaazouzi, Zakaria
    Outzourhit, Abdelkader
    El Alami, Mustapha
    Bennouna, El Ghali
    PROCEEDINGS OF CHT-21 ICHMT INTERNATIONAL SYMPOSIUM ON ADVANCES IN COMPUTATIONAL HEAT TRANSFER, 2021, 2021,
  • [6] Numerical thermal performance analysis of a PCM-to-air and liquid heat exchanger implementing latent heat thermal energy storage
    Momeni, Mahdi
    Fartaj, Amir
    JOURNAL OF ENERGY STORAGE, 2023, 58
  • [7] Experimental and numerical analysis of a cement based thermal energy storage system with a helical heat exchanger
    Nordbeck, Johannes
    Beyer, Christof
    Bauer, Sebastian
    APPLIED THERMAL ENGINEERING, 2021, 185
  • [8] Performance and energy efficiency analysis of data center cooling plant by using lake water source
    Ling, Li
    Zhang, Quan
    Zeng, Liping
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 3096 - 3103
  • [9] Dynamic performance analysis and thermal modelling of a novel two-phase spray cooled rack system for data center cooling
    Liu, Pengfei
    Kandasamy, Ranjith
    Ho, Jin Yao
    Wong, Teck Neng
    Toh, Kok Chuan
    ENERGY, 2023, 269
  • [10] Energy efficiency optimization of an integrated heat pipe cooling system in data center based on genetic algorithm
    He, Zhiguang
    Xi, Haonan
    Ding, Tao
    Wang, Jianmin
    Li, Zhen
    APPLIED THERMAL ENGINEERING, 2021, 182