Unit Commitment of Power System With High Proportion of Wind Power Considering Frequency Safety Constraints

被引:0
|
作者
Lin H. [1 ]
Hou K. [2 ]
Chen L. [1 ]
Xia D. [2 ]
Min Y. [1 ]
Qin S. [2 ]
Zhang B. [2 ]
机构
[1] State Key Lab of Control and Simulation of Power System and Generation Equipment, Department of Electrical Engineering, Tsinghua University, Haidian District, Beijing
[2] Northeast Branch of State Grid Corporation of China, Shenyang
来源
Chen, Lei (chenlei08@tsinghua.edu.cn) | 1600年 / Power System Technology Press卷 / 45期
基金
中国国家自然科学基金;
关键词
Active power and frequency control; Frequency safety; Linearization; Primary frequency regulation; Unit commitment; Wind power uncertainty;
D O I
10.13335/j.1000-3673.pst.2020.0190a
中图分类号
学科分类号
摘要
The connection of high proportion of wind power into the power system results in the reduction of the system inertia and the primary frequency regulation capability, which may highlight the issue of frequency safety under power disturbances. Therefore, the frequency safety constraints need to be considered in the unit commitment. First, a simple and practical frequency safety constraint is proposed. When the system satisfies this constraint, the maximum frequency deviation under a given power disturbance remains in the set range. By incorporating this constraint into the unit commitment model, and on the basis that the system can still bear the corresponding power disturbances when the wind power output is in the extreme case, an unit commitment model is established considering the wind power uncertainty and the frequency safety constraints. Simulation results show that the proposed unit commitment model takes into account the uncertainty of wind power, and can also meet the frequency safety needs of the system under high power disturbances. © 2021, Power System Technology Press. All right reserved.
引用
收藏
页码:1 / 9
页数:8
相关论文
共 30 条
  • [1] Hu Yi, Wang Xiaoru, A dynamic frequency analysis method for HVDC-interconnected asynchronous power grid considering emergency power support, Power System Technology, 42, 9, pp. 2859-2868, (2018)
  • [2] Zheng Chao, Wang Shiyuan, Zhang Boqi, Et al., Dynamic frequency characteristics and countermeasures of power grid with highly penetrated photovoltaics, Power System Technology, 43, 11, pp. 4064-4073, (2019)
  • [3] Chang Yekui, Liu Rao, Ba Yu, Et al., Frequency control mode and performance assessment in UHV grid with high proportion of renewable energy resources, Power System Technology, 43, 2, pp. 621-629, (2019)
  • [4] Xia Qing, Zhong Haiwang, Kang Chongqing, Development and prospect of safety-constrained unit combination theory and application, Proceedings of the CSEE, 33, 16, pp. 123-132, (2013)
  • [5] Zhang Li, Zhao Jianguo, Han Xueshan, New algorithm for generating unit combination considering network security constraints, Power System Technology, 30, 21, pp. 50-55, (2006)
  • [6] Yang Pengpeng, Han Xueshan, Zha Hao, An effective algorithm considering static safety constrained unit combination, Automation of Electric Power Systems, 33, 8, pp. 39-43, (2009)
  • [7] Jiang Quanyuan, Zhang Mingze, Gao Qiang, Parallel solution of unit combination considering AC power flow constraints, Transactions of China Electrotechnical Society, 24, 8, pp. 120-126, (2009)
  • [8] (2010)
  • [9] Xu Y, Dong Z Y, Zhang R, Et al., A decomposition-based practical approach to transient stability-constrained unit commitment[J], IEEE Transactions on Power Systems, 30, 3, pp. 1455-1464, (2015)
  • [10] Lin Tao, Ye Jing, Chen Rusi, Et al., Research on unit combination of large-scale wind power system with steady frequency constraints [J], Journal of Electric Power Science and Technology, 29, 4, pp. 18-24, (2014)