Evaluating common supply air temperature setpoint reset strategies with varying occupancy patterns and behaviours

被引:0
|
作者
Elehwany, Hussein [1 ]
Gunay, Burak [1 ]
Ouf, Mohamed [2 ]
Cotrufo, Nunzio [3 ]
Venne, Jean-Simon [3 ]
机构
[1] Carleton Univ, Dept Environm Engn, 1125 Colonel By Dr, Ottawa, ON K1S5B6, Canada
[2] Concordia Univ, Dept Bldg Civil & Environm Engn, 1515 St Catherine W, Montreal, PQ H3G1S6, Canada
[3] BrainBox AI Inc, 2075 Blvd Robert Bourassa, Montreal, PQ H3A2L1, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Occupant centric controls; Supply air temperature reset strategy; Trim and respond logic; Occupancy patterns; Occupant thermal preferences; BUILDING CONTROL; THERMAL COMFORT; SYSTEM; ENERGY; OPTIMIZATION; SIMULATION; VALIDATION; EFFICIENCY;
D O I
10.1016/j.buildenv.2024.112129
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The supply air temperature (SAT) setpoint of a multi-zone variable air volume (VAV) air handling unit (AHU) systems significantly affects the system's performance. ASHRAE Guideline 36 introduces a so-called trim and respond logic defining the SAT reset behaviour of these systems. The trim and respond logic for SAT reset relies on demand-based feedback. Many studies have assessed ASHRAE Guideline 36, however there is a literature gap in addressing the performance of the trim and respond SAT reset with varying occupancy patterns and behaviours. This paper studies four SAT reset strategies under different thermal preferences and irregular occupancy patterns: (1) constant 13 degrees C SAT, (2) SAT reset based on outdoor air temperature (OAT), (3) trim and respond, and (4) trim and respond combined with OAT reset. Different cases of zone-level setpoints and irregular occupancy schedules have been simulated in EnergyPlus with the studied SAT setpoint reset methods. The results show that varying setpoints across different zones lead to higher energy use with all studied SAT reset strategies. The highest variation in energy use was accompanied with constant SAT, with a standard deviation of 16 kWh/m(2), and the highest variation in averaged discomfort fraction was accompanied with OAT reset, with a standard deviation of 5.3%. Both trim and respond methods achieved better comfort results with varying setpoints. These findings establish a basis for future work on developing a SAT reset strategy that utilizes occupant-centric control (OCC) that optimally balances thermal comfort and energy use.
引用
收藏
页数:15
相关论文
共 9 条
  • [1] Evaluation of a cost-responsive supply air temperature reset strategy in an office building
    Raftery, Paul
    Li, Shuyang
    Jin, Baihong
    Ting, Min
    Paliaga, Gwelen
    Cheng, Hwakong
    ENERGY AND BUILDINGS, 2018, 158 : 356 - 370
  • [2] Choosing the Right Parameter for Single-Duct Constant Air Volume System Supply Air Temperature Reset
    Wei, G.
    Claridge, D. E.
    Turner, W. D.
    Liu, M.
    JOURNAL OF ARCHITECTURAL ENGINEERING, 2005, 11 (03) : 76 - 80
  • [3] Alternative strategies for supply air temperature control in office buildings
    Gruber, Mattias
    Truschel, Anders
    Dalenback, Jan-Olof
    ENERGY AND BUILDINGS, 2014, 82 : 406 - 415
  • [4] Evaluating the effects of capacity constraints and demand patterns on supply chain replenishment strategies
    Suwanruji, P.
    Enns, S. T.
    INTERNATIONAL JOURNAL OF PRODUCTION RESEARCH, 2006, 44 (21) : 4607 - 4629
  • [5] Experimental study on the room temperature uniformity with air supply and back patterns
    Wu, Hongmei
    Zhang, Yong
    Wang, Xin
    Zhou, Rong
    PROCEEDINGS OF THE 2015 INTERNATIONAL FORUM ON ENERGY, ENVIRONMENT SCIENCE AND MATERIALS, 2015, 40 : 1645 - 1652
  • [6] Evaluation of supply air temperature control performance with different control strategies at air handling units
    Wang, Zufen
    Hashem, Marwan R.
    Song, Li
    Wang, Gang
    BUILDING AND ENVIRONMENT, 2023, 243
  • [7] New Optimal Supply Air Temperature and Minimum Zone Air Flow Resetting Strategies for VAV Systems
    Nassif, Nabil
    Tahmasebi, Mostafa
    Ridwana, Iffat
    Ebrahimi, Pejman
    BUILDINGS, 2022, 12 (03)
  • [8] Study on the transition patterns of the oblique detonation wave with varying temperature of the hydrogen-air mixture
    Qin, Qiongyao
    Zhang, Xiaobing
    FUEL, 2020, 274 (274)
  • [9] A Network-Based Strategy to Increase the Sustainability of Building Supply Air Systems Responding to Unexpected Temperature Patterns
    Ahn, Jonghoon