An experimental comparative analysis and machine learning prediction on the evaporation characteristics of R1234yf and R290/R13I1 in a plate heat exchanger

被引:0
|
作者
Prabakaran, Rajendran [1 ]
Dhamodharan, Palanisamy [1 ]
Mohanraj, Thangamuthu [2 ]
Kim, Sung Chul [1 ]
机构
[1] Yeungnam Univ, Sch Mech Engn, 280 Daehak Ro, Gyongsan 712749, Gyeongbuk, South Korea
[2] Amrita Vishwa Vidyapeetham, Dept Mech Engn, Amrita Sch Engn Coimbatore, Coimbatore, India
关键词
Evaporation characteristics; R1234yf; Experimental analysis; Machine learning prediction; Heat transfer coefficient; Frictional pressure drop; R290/R13I1; PRESSURE-DROP; TRANSFER COEFFICIENT; FLOW; R134A;
D O I
10.1016/j.icheatmasstransfer.2024.108357
中图分类号
O414.1 [热力学];
学科分类号
摘要
The present research attempts to comprehensively compare the evaporation characteristics of a novel R290/R13I1 (35/65 % by mass) with R1234yf in an offset-strip fin embedded plate heat exchanger. The impact of various testing phenomena, namely saturation temperature (T-s) (278 to 288 K), heat flux (q) (4000 to 10,000 W m(-2)), entry vapor quality (x(i)) (0.1 to 0.8), and mass flux (G) (40 to 80 kg m(-2) s(-1)) have been explored. Meanwhile, highly potential machine learning algorithms (MLAs) namely Linear Regression (LR), Multi-Layer Perceptron (MLP), and Extreme Gradient Boost regression (XGB) have been employed to predict the evaporation heat transfer coefficient (EHTC) and evaporation frictional pressure drop (EFPD) of the refrigerants. Findings revealed that the EHTC of R290/R13I1 is significantly lower than that of R1234yf by 7.9-38.8 % in the nucleation boiling or low mean vapor quality (x(m)) domain, whereas it had superior EHTC by up to 18.2 % in the convective boiling domain (high x(m)). Interestingly, there was a dry-out incidence at mid-x(m) ranges (0.35-0.5) for both refrigerants, except for R290/R13I1 at a higher G of 80 kg m(-2) s(-1). In all cases (except at 10000 W m(-2)), the EFPD of R290/R13I1 increased by 0.3-11.1 % compared to that of R1234yf. The evaporation thermo-hydraulic performance (ETHP) factor analysis revealed that utilizing R290/R13I1 could perform satisfactorily in the convective boiling domain (x(m) > 0.5) with an ETHP factor ranging between 0.8 and 1.08, especially at high q, high T-s, and low G conditions. New empirical correlations have been developed based on the experimental dataset for the EHTC and EFPD of the considered refrigerants with an mean absolute error (MAE) of up to 14.7 % and 13.4 %, respectively. Among the three MLAs with different enhancement methods, the EHTC and EFPD predictions using MLP, in combination with principal component analysis and hyperparameter tuning, had superior performance, with MAEs of 0.1119 and 0.0581, respectively, for R1234yf, while they were 0.1726 and 0.0482 for R290/R13I1.
引用
收藏
页数:24
相关论文
共 50 条
  • [1] Experimental comparison and optimal machine learning technique for predicting the thermo-hydraulic performance of Low-GWP refrigerants (R1234yf, R290, and R13I1/R290) during evaporation in plate heat exchanger
    Prabakaran, Rajendran
    Mohanraj, Thangamuthu
    Dhamodharan, Palanisamy
    Kim, Sung Chul
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 64
  • [2] Comparative analysis of R290 and R1234yf cooling performance in offset strip-fin plate heat exchanger for electric-vehicle battery thermal management
    Dhamodharan, Palanisamy
    Salman, Mohammad
    Prabakaran, Rajendran
    Kim, Sung Chul
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2024, 157
  • [3] Experimental and numerical investigation of thermal performances of R290 and R1234yf refrigerants in a cold room
    DAS, M. E. H. M. E. T.
    PEKTEZEL, O. G. U. Z. H. A. N.
    ALIC, E. R. D. E. M.
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2022, 28 (08) : 970 - 984
  • [4] Performance comparison of a direct heat pump using R1234yf and indirect heat pumps using R1234yf and R290 designed for cabin heating of electric vehicles
    Kwon, Soonbum
    Lee, Dongchan
    Chung, Jun Yeob
    Maeng, Heegyu
    Kim, Yongchan
    ENERGY, 2024, 297
  • [5] Study of a Heat Pump for Simultaneous Heating and Cooling Working with R290 or R1234yf and Coupled to a Building
    Ghoubali, Redouane
    Byrne, Paul
    Miriel, Jacques
    Bazantay, Frederic
    2013 ASHRAE ANNUAL CONFERENCE, 2013,
  • [6] Experimental investigation on combustion characteristics of flammable refrigerant R290/R1234yf leakage from heat pump system for electric vehicles
    Li, Kang
    Wang, Jingwu
    Luo, Shuxian
    Wang, Zhenzhen
    Zhou, Xuejin
    Fang, Jun
    Su, Lin
    Tu, Ran
    ROYAL SOCIETY OPEN SCIENCE, 2020, 7 (04):
  • [7] Comparative analysis of flow boiling characteristics of an R290/R1270 mixture and R290 in a plate heat exchanger with offset strip fins
    Salman, Mohammad
    Prabakaran, Rajendran
    Lee, Dongchan
    Kim, Sung Chul
    APPLIED THERMAL ENGINEERING, 2023, 227
  • [8] Heat transfer and pressure drop characteristics of R1234yf during evaporation in a plate heat exchanger with offset strip fins: An experimental study
    Prabakaran, Rajendran
    Salman, Mohammad
    Kumar, Poongavanam Ganesh
    Lee, Dongchan
    Kim, Sung Chul
    International Journal of Heat and Mass Transfer, 2022, 194
  • [9] Heat transfer and pressure drop characteristics of R1234yf during evaporation in a plate heat exchanger with offset strip fins: An experimental study
    Prabakaran, Rajendran
    Salman, Mohammad
    Kumar, Poongavanam Ganesh
    Lee, Dongchan
    Kim, Sung Chul
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2022, 194
  • [10] FEASIBILITY OF R1234yf/R13I1 MIXTURE REFRIGERANT AS REPLACEMENT OF R134a REFRIGERANT IN VAPOR COMPRESSION SYSTEM
    Yang, Weibing
    Meng, Zhaofeng
    Huo, Ziheng
    Ding, Chuangchuang
    THERMAL SCIENCE, 2024, 28 (3A): : 2083 - 2092