Influence of three-phase imbalance and harmonic on line loss of three-phase four-wire low-voltage distribution network

被引:0
|
作者
Xie R. [1 ]
Du F. [1 ]
Cheng X. [2 ]
Zhou Q. [2 ]
Xu F. [2 ]
机构
[1] Guiyang Xifeng Power Supply Bureau of Guizhou Power Grid, Guiyang
[2] School of Electrical Engineering, Sichuan University, Chengdu
基金
中国国家自然科学基金;
关键词
Chroma 6590 programmable AC source; Harmonic; Line loss; Matlab/Simulink; Three-phase imbalance;
D O I
10.19783/j.cnki.pspc.191561
中图分类号
学科分类号
摘要
Aiming at problem of line loss in a three-phase four-wire low voltage distribution network, this paper presents a method for calculating line loss under the action of composite power quality and compares it with that under the action of single power quality. First, the line loss caused by three-phase imbalance is deduced. Secondly, the line loss under harmonic condition is derived according to the superposition principle. Then the line losses under the combined action of the two power qualities are comprehensively considered and derived, and the line losses under the combined action of the two power qualities are compared by the symmetric component method. The results show that the three-phase imbalance aggravates the harmonic loss, that is, the line loss when the harmonic and the three phase unbalance exist together is greater than the sum of the line loss when they exist separately. Finally, the Matlab/Simulink simulation tool and chroma 6590 programmable AC source experiment are used to test each part and verify the correctness of the theoretical derivation. © 2020, Power System Protection and Control Press. All right reserved.
引用
下载
收藏
页码:22 / 30
页数:8
相关论文
共 30 条
  • [1] YIN Zhongdong, ZHANG Jing, Study on loss of key equipment in power distribution network under composite power quality disturbance, Electrical Applications, 38, 3, pp. 12-20, (2019)
  • [2] YANG Wenfeng, WANG Binyu, CHENG Zhuo, Et al., Optimized decision approach of loss reduction plan for medium-and low-voltage urban distribution networks, Power System Technology, 38, 9, pp. 2598-2604, (2014)
  • [3] GAO Junqin, The circuit loss rate analysis of three-phase unbalanced circuit, Journal of Electric Power, 16, 2, pp. 91-93, (2001)
  • [4] HUAI Quan, HOU Xiaohu, HE Liangce, Et al., A method of state estimation for middle voltage and low voltage distribution network with distributed generations, Power System Protection and Control, 46, 21, pp. 69-77, (2018)
  • [5] WU Zhili, WANG Xuyang, Reflections on the implementation of the 13th five-year plan for distribution network, Electric Power, 50, 1, pp. 25-29, (2017)
  • [6] LIU Kaijun, Thoughts on several major issues in the 13th five-year plan for power grid, Journal of State Grid
  • [7] XU Qin, LIU Jinsong, HAN Weifu, Et al., Status quo and development trend of distribution network construction, East China Electric Power, 41, 12, pp. 2532-2535, (2013)
  • [8] MENG Xiaoli, LI Huiling, SHENG Wanxing, Development and implementation of line loss systematic management system for provincial, municipal and county distribution networks, Automation of Electric Power Systems, 29, 23, pp. 87-90, (2005)
  • [9] FENG Cheng, XU Changbao, LI Huaiyu, Et al., Analysis of three phase current unbalance and harmonic influence on power loss, Electrical Applications, 35, 13, pp. 47-52, (2016)
  • [10] NI Feng, YU Jianming, PAN Zhongmei, Low-voltage distribution network theoretical energy loss calculation based on real-time unbalance in three phrases, Journal of Xi'an University of Technology, 24, 3, pp. 349-354, (2008)