Multilevel sub-module topology of MMC with DC fault clearance capability

被引:0
|
作者
Chang F. [1 ]
Yang Z. [1 ]
Lin F. [1 ]
机构
[1] School of Electrical Engineering, Beijing Jiaotong University, Beijing
来源
关键词
DC fault; Fault clearance; HVDC; MMC; Sub-module topology; System recovery;
D O I
10.13336/j.1003-6520.hve.20161227007
中图分类号
学科分类号
摘要
DC fault clearance capacity of MMC-HVDC is directly related to the application of MMC-HVDC in the field of overhead lines and high voltage and large capacity applications. Consequently, we proposed a new kind of MMC improved topology. The capacitor voltage of the sub-module produced counter electromotive was used to forcibly eliminate the freewheeling effect of diodes, and to quickly remove the fault current. The principle of DC fault clearing and the voltage resistance of each power device are analyzed in detail, and the comparison with other topologies is also carried out. Moreover, the correctness and effectiveness of the new sub-module is verified by PSCAD/EMTDC simulation. The results show that the rated voltages of main IGBT and protection IGBT of the proposed topology are only half of the conventional design which can effectively reduce the cost of converter. © 2017, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:44 / 49
页数:5
相关论文
共 17 条
  • [1] Tang G., He Z., Pang H., Research, application and development of VSC-HVDC engineering technology, Automation of Electric Power Systems, 37, 15, pp. 3-14, (2013)
  • [2] Li X., Liu W., Song Q., Et al., An enhanced MMC topology with DC fault clearance capability, Proceedings of the CSEE, 34, 36, pp. 6389-6397, (2014)
  • [3] Xiang W., Lin W., Wen J., Et al., A new topology of sub-modules with DC fault current blocking capability and a new type of hybrid MMC converter, Proceedings of the CSEE, 34, 29, pp. 5171-5179, (2014)
  • [4] Wang S., Zhou X., Tang G., Et al., Analysis of submodule overcurrent caused by DC pole-to-pole fault in modular multilevel converter HVDC system, Proceedings of the CSEE, 31, 1, pp. 1-7, (2011)
  • [5] Zhao C., Chen X., Cao C., Et al., Control and protection strategies for MMC-HVDC under DC faults, Automation of Electric Power Systems, 35, 23, pp. 82-87, (2011)
  • [6] Ding Y., Su J., Zhou J., Analysis on fault current limitation and self-recovery of MMC based on clamp double sub-module, Automation of Electric Power Systems, 38, 1, pp. 97-103, (2014)
  • [7] High-voltage Direct Current(HVDC) Transmission Using Voltage Sourced Converters(VSC), (2011)
  • [8] Marquardt R., Modular multilevel converter topologies with DC-short circuit current limitation, Proceedings of IEEE Energy Conversion Congress and Exposition, pp. 1425-1431, (2011)
  • [9] Zhao P., Wang C., Xu J., Et al., A sub-module topology of MMC with DC fault ride-through capability, Power System Technology, 38, 12, pp. 3441-3446, (2014)
  • [10] Wang Y., Liu J., An enhanced MMC-HVDC topology and system recovery strategy for DC fault protection, Power System Technology, 39, 8, pp. 2312-2319, (2015)