Test and Analysis of Transfer Characteristics of Electronic Current Transformer

被引:0
|
作者
Zhu M. [1 ,2 ,3 ]
Luo Q. [4 ]
Cao M. [2 ,3 ]
Shu H. [1 ]
Tian X. [1 ]
Zhai S. [2 ,3 ]
机构
[1] Faculty of Land Resources Engineering, Kunming University of Science and Technology, Kunming
[2] Electric Power Research Institute of Yunnan Power Grid Co. Ltd., Kunming
[3] Key Laboratory of CSG for Electric Power Measurement, Kunming
[4] Jiangsu Ling Chuang Electric Automation Co. Ltd., Zhenjiang
基金
中国国家自然科学基金;
关键词
Electronic current transformer; Frequency aliasing; Frequency response; Measurement accuracy; Transient characteristics;
D O I
10.7500/AEPS20171106004
中图分类号
学科分类号
摘要
At present, due to the lack of an effective and practical integrated test platform, there are few tests on measurement accuracy and protection transfer characteristics of electronic current transformers (ECTs) with different principles under actual working conditions. This paper analyzes the key factors and links that affect the accuracy and transfer characteristics of ECT and develops a platform for simulating the performance of electronic transformers under different operation loads, environmental conditions, power factors, communication anomalies and primary side faults. The ECT steady state accuracy test, the ECT harmonic characteristics and frequency aliasing test and the ECT transient characteristic test under the fault are carried out. Through the test of ECTs of different manufacturers and different principles, it is found that the measurement accuracy and stability of low power current transformer (LPCT) are better than that of all-fiber optic current transformer (FOCT) in terms of steady-state error. With the increase of frequency, the ratio error of LPCT is relatively stable, and the Rogowski coil will increase, and the phase error shows an overall increasing trend. There are varying degrees of frequency aliasing in ECT of various manufacturers. FOCT can reliably transmit transient parameters caused by fault, while LPCT is easy to saturate under DC component, and the Rogowski coil is greatly affected by integral link, which causes serious error. © 2018 Automation of Electric Power Systems Press.
引用
收藏
页码:143 / 149
页数:6
相关论文
共 17 条
  • [1] Shang Q., Zhang J., Dong J., Evaluation of measurement uncertainty for the calibration system of electronic current transformer, Automation of Electric Power Systems, 32, 18, pp. 63-66, (2008)
  • [2] Fu C., Rao H., Li X., HVDC 50 Hz and 100 Hz protection of AC/DC hybrid transmission system, Automation of Electric Power Systems, 32, 12, pp. 57-60, (2008)
  • [3] Xiao H., Liu B., Wan S., Et al., Temperature error compensation technology of all-fiber optical current transformers, Automation of Electric Power Systems, 35, 21, pp. 91-95, (2011)
  • [4] Shao X., Peng H., Wang N., Electronic voltage transformer based on double integrator for power quality detection in smart grid, Automation of Electric Power Systems, 41, 13, pp. 156-161, (2017)
  • [5] Xu Y., Zhu K., Zhang Y., Et al., Operation and analysis of direct current optical-electronic current transformer, Automation of Electric Power Systems, 32, 13, pp. 97-100, (2008)
  • [6] Bohnert K., Gabus P., Nehring J., Et al., Temperature and vibration insensitive fiber-optic current sensor, Journal of Lightwave Technology, 20, 2, pp. 267-276, (2002)
  • [7] Li Z., Li C., Li Z., Et al., A high accuracy on-line calibration method for electronic voltage transformers with digital output, Automation of Electric Power Systems, 39, 13, pp. 163-167, (2015)
  • [8] Tong Y., Li H., Zhang M., Et al., A full digital high voltage current transformer online calibration system, Transactions of China Electrotechnical Society, 24, 8, pp. 59-64, (2010)
  • [9] Ma Y., Huang M., The development of digital output of electronic transformer calibration system, Power System Protection and Control, 38, 1, pp. 83-86, (2010)
  • [10] Yao D., Lyu L., Ni C., Et al., Dual loop digital integrator design for Rogowski coil electronic transformer, Automation of Electric Power Systems, 40, 6, pp. 96-100, (2016)