Study on AC Insulation Resistance Measurement Method for Power Cable

被引:0
|
作者
Kamohara, Hiroaki [1 ]
Ehara, Yoshiyasu [2 ]
机构
[1] Dyden Corporation, 3330, Nakatsukuma, Miyaki-cho, Miyaki-gun, Saga,849-0114, Japan
[2] Tokyo City University, 1-28-1, Tamazutsumi, Setagaya-ku, Tokyo,158-8557, Japan
关键词
Insulation - Deterioration - Electric resistance measurement - Cable sheathing;
D O I
10.1541/ieejfms.140.508
中图分类号
学科分类号
摘要
In 1989, the low-frequency superposition method was developed as an online diagnostic method for XLPE cables for 6 kV power distribution, and its application to the field has started. However, various problems became clear, and the authors developed the AC insulation resistance measurement method in 1993 with the aim of solving these problems. Since then, the results of online diagnostics using AC insulation resistance measurement have been accumulated, and the ability to detect deterioration of water trees has been confirmed to be excellent. However, there are unclear points such as the measurement range and the validity of the measurement results. Therefore, the validity of the measurement range and measurement results was verified by numerical calculation using an equivalent circuit. © 2020 The Institute of Electrical Engineers of Japan.
引用
收藏
页码:508 / 515
相关论文
共 50 条
  • [1] An on-line bridge method for cable insulation resistance measurement
    Wei, XL
    Ma, S
    Chen, QG
    Zhu, JL
    Wang, YH
    [J]. JOINT CONFERENCE OF 96' AICDEI / 4T-JCCEID, 1996, : 373 - 376
  • [2] DIAGNOSTIC METHOD FOR POWER CABLE INSULATION
    SOMA, K
    AIHARA, M
    KATAOKA, Y
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1986, 21 (06): : 1027 - 1032
  • [3] Additional low frequency signal measurement method of insulation resistance about mine cable
    Lei, Li
    Zhong, Li
    [J]. 2016 INTERNATIONAL SYMPOSIUM ON COMPUTER, CONSUMER AND CONTROL (IS3C), 2016, : 891 - 894
  • [4] The study of inhomogeneities effect on the insulation of a power cable
    Popa, Monica
    Pasca, Sorin
    [J]. 2019 15TH INTERNATIONAL CONFERENCE ON ENGINEERING OF MODERN ELECTRIC SYSTEMS (EMES), 2019, : 189 - 192
  • [5] POWER CABLE INSULATION
    SUZUKI, K
    SAITO, S
    YOSHIDA, S
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1986, 21 (06): : 945 - 952
  • [6] A Power Cable Thermal Aging Insulation Resistance Degradation Model
    Ge, Xufei
    Given, Martin
    Stewart, Brian G.
    [J]. 2022 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP 2022), 2022, : 53 - 56
  • [7] Study on Methodology Monitoring Power Cable Insulation Defects
    Quan, Yusheng
    Qi, Shiwei
    Zhou, Enze
    Wang, Beibei
    Zhao, Bo
    [J]. ENERGY AND POWER TECHNOLOGY, PTS 1 AND 2, 2013, 805-806 : 839 - +
  • [8] COMPOSITE INSULATION FOR A POWER CABLE
    SALAMA, MMA
    HACKAM, R
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING EDUCATION, 1985, 22 (03) : 229 - 232
  • [9] SUPERCONDUCTING HIGH-POWER AC CABLE - DEVELOPMENT OF CONDUCTORS AND MEASUREMENT OF THEIR AC LOSSES
    BOGNER, G
    PENCZYNSKI, P
    SCHMIDT, F
    [J]. SIEMENS FORSCHUNGS-UND ENTWICKLUNGSBERICHTE-SIEMENS RESEARCH AND DEVELOPMENT REPORTS, 1979, 8 (01): : 8 - 15
  • [10] Diagnostic markers for ac power cable insulation aging based on space charge measurements
    Montanari, GC
    Fabiani, D
    Melloni, M
    Palmieri, F
    [J]. CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, : 464 - 467