Data-driven Method and Interpretability Analysis for Transient Voltage Stability Assessment

被引:0
|
作者
Zhou T. [1 ]
Yang J. [1 ]
Zhan X. [1 ]
Pei Y. [1 ]
Zhang J. [1 ]
Chen H. [1 ]
Zhu F. [2 ]
机构
[1] School of Electrical Engineering and Automation, Wuhan University, Wuhan
[2] State Key Laboratory for Management and Control of Complex Systems, Institute of Automation (Chinese Academy of Sciences), Haidian District, Beijing
来源
关键词
Catboost model; Data-; driven; Interpretability; Shapley value; Transient voltage stability assessment;
D O I
10.13335/j.1000-3673.pst.2020.2170
中图分类号
学科分类号
摘要
Data-driven methods for the power system transient voltage stability assessment (TVSA) can give consideration to both the accuracy and the speed of prediction. But these methods exist some problems like poor generalization performance, weak interpretability, or else. Some physical quantities collected after the faults are selected as the input to establish the TVSA model based on the gradient boosting algorithm with categorical features support (Catboost). The ordered boosting method is proposed to avoid the prediction shift and increase the accuracy. The oblivious decision trees are adopted to improve the calculation efficiency. Meanwhile, the cost-sensitive strategy is applied to solve the problem of class imbalance. An attribution analysis framework for TVSA based on the SHAP theory is proposed in order to improve the interpretability. The importance ranking of the input features are carried out according to the average absolute value of the Shapley value. The effect of different features on the model's outputs are further quantified by the marginal contributions of the features. Case studies on the IEEE 39-bus system show that the proposed classifier has higher prediction accuracy and speed. The attribution analysis method based on the Shapley value is effective in illustrating the impact of different features on the transient voltage stability and the prediction results of the machine learning model. © 2021, Power System Technology Press. All right reserved.
引用
收藏
页码:4416 / 4425
页数:9
相关论文
共 41 条
  • [1] LIN Weifang, SUN Huadong, TANG Yong, Et al., Analysis and lessons of the blackout in Brazil power grid on November 10, 2009, Automation of Electric Power Systems, 34, 7, pp. 1-5, (2010)
  • [2] TANG Yong, BU Guangquan, YI Jun, Analysis and lessons of the blackout in Indian power grid on July 30 and 31, 2012, Proceedings of the CSEE, 32, 25, pp. 167-174, (2012)
  • [3] YU J J Q, HILL D J, LAM A Y S, Et al., Intelligent time-adaptive transient stability assessment system, IEEE Transactions on Power Systems, 33, 1, pp. 1049-1058, (2018)
  • [4] (2019)
  • [5] (2016)
  • [6] WU Wei, TANG Yong, SUN Huadong, Et al., The recognition of principal mode between rotor angle instability and transient voltage instability, Proceedings of the CSEE, 34, 31, pp. 5610-5617, (2014)
  • [7] (2020)
  • [8] WU Wei, TANG Yong, SUN Huadong, Et al., A survey on research of power system transient stability based on wide-area measurement information, Power System Technology, 36, 9, pp. 81-87, (2012)
  • [9] XUE Yusheng, A critical comparison of various methods for transient stability assessment part one disturbed-measure functions, Automation of Electric Power Systems, 25, 11, pp. 6-11, (2001)
  • [10] LIU Jiuliang, WANG Tong, ZHU Shaoxuan, Et al., An analytic method for power system transient stability margin considering protection information, Transactions of China Electrotechnical Society, 35, 3, pp. 542-552, (2020)