Quantifying ventilation effectiveness for air quality control

被引:0
|
作者
Zhang, Y. [1 ]
Wang, X. [1 ]
Riskowski, G.L. [1 ]
Christianson, L.L. [1 ]
机构
[1] 332 C. 1304 W. Pennsylvania Ave., Urbana, IL 61801, United States
关键词
Agriculture - Air quality - Farms - Ventilation;
D O I
暂无
中图分类号
学科分类号
摘要
The term ventilation effectiveness has been widely used to evaluate ventilation systems for air quality control. The application of the term is often either qualitative, rather than quantitative, or difficult for field application. This paper presents the results of quantification of ventilation effectiveness for specific ventilation systems by using a ventilation effectiveness factor (VEF) and a ventilation effectiveness map (VEM). The VEF and VEM are defined mathematically so they can be used to quantify the ventilation effectiveness of a ventilation system. The application of the VEF and VEM was illustrated using a full-scale room case study, which involves comparison of two different ventilation systems: one had a slot air outlet at the opposite wall to the air inlet (Case A), and the other had a air outlet at the same wall as the air inlet (Case B). It is commonly assumed that the locations of air outlets or exhaust fans have little effect on the ventilation effectiveness for livestock buildings. The case studies show that the outlet location had a substantial effect on the ventilation effectiveness for the room airspace as a whole and for specific locations in the room. The differences in ventilation effectiveness for these two systems were quantified in terms of VEF. Ventilation in Case B is three times as effective at dust removal as in Case A. Ventilation effectiveness factors at specific locations within the airspace were also plotted on a VEM. One of advantages of VEF is that a ventilation system can be its own control for comparison of ventilation effectiveness, instead of requiring a control and a treatment. This feature is particularly useful in system evaluation or troubleshooting because it is often very difficult and expensive to have an identical system to compare.
引用
收藏
页码:385 / 390
相关论文
共 50 条
  • [1] Quantifying ventilation effectiveness for air quality control
    Zhang, YH
    Wang, X
    Riskowski, GL
    Christianson, LL
    TRANSACTIONS OF THE ASAE, 2001, 44 (02): : 385 - 390
  • [2] A method to quantify ventilation effectiveness for air quality control
    Zhang, YH
    Wang, XL
    Riskowski, GL
    Christianson, LL
    AIR POLLUTION FROM AGRICULTURAL OPERATIONS, PROCEEDINGS, 2000, : 329 - 336
  • [3] Improving indoor air quality by increased ventilation effectiveness
    Rojeski, Jr., Peter
    Journal of Architectural Engineering, 1999, 5 (01) : 25 - 29
  • [4] EFFECTIVENESS OF INDOOR AIR QUALITY IMPROVEMENT WITH OUTDOOR AIR FOR BUILDING VENTILATION
    Wang, J.
    Zhang, X.
    Zhou, X.
    7TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, PROCEEDINGS OF ISHVAC 2011, VOLS I-IV, 2011, : 417 - 421
  • [5] Modeled Effectiveness of Ventilation with Contaminant Control Devices on Indoor Air Quality in a Swine Farrowing Facility
    Anthony, T. Renee
    Altmaier, Ralph
    Park, Jae Hong
    Peters, Thomas M.
    JOURNAL OF OCCUPATIONAL AND ENVIRONMENTAL HYGIENE, 2014, 11 (07) : 434 - 449
  • [6] Air quality in an underground garage: computational and experimental investigation of ventilation effectiveness
    Papakonstantinou, K
    Chaloulakou, A
    Duci, A
    Vlachakis, N
    Markatos, N
    ENERGY AND BUILDINGS, 2003, 35 (09) : 933 - 940
  • [7] A review of ventilation and the quality of ventilation air
    Liddament, MW
    INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 2000, 10 (03): : 193 - 199
  • [8] Ventilation control for improved cabin air quality and vehicle safety
    Galatsis, K
    Wlodarski, W
    Li, YX
    Kalantar-zadeh, K
    IEEE VTC 53RD VEHICULAR TECHNOLOGY CONFERENCE, SPRING 2001, VOLS 1-4, PROCEEDINGS, 2001, : 3018 - 3021
  • [9] Air quality control in mine refuge chamber with ventilation through pressure air pipeline
    Zhang, Zujing
    Wu, Hongwei
    Wang, Kequan
    Day, Rodney
    Yuan, Yanping
    PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2020, 135 : 46 - 58
  • [10] Effectiveness of in-room air filtration and dilution ventilation for tuberculosis infection control
    MillerLeiden, S
    Lobascio, C
    Nazaroff, WW
    Macher, JM
    JOURNAL OF THE AIR & WASTE MANAGEMENT ASSOCIATION, 1996, 46 (09) : 869 - 882