Research on detecting single-phase-to-ground faulted feeder in resonant grounded power distribution system

被引:0
|
作者
Chen, Kui [1 ]
Tang, Yi [1 ]
Liu, Changjiang [1 ]
Dong, Haibo [1 ]
机构
[1] China University of Mining and Technology, Xuzhou 221008, China
来源
关键词
D O I
暂无
中图分类号
学科分类号
摘要
In the resonant grounded power distribution system, the magnitude and direction of zero sequence measuring current in the faulty line is different from the current in the ungrounded power system when a single phase earth fault happens because of the compensation effect of the inductive current in arc suppression coil on the capacity ground current. Because the magnitude of zero sequence measuring current is connected with the compensation degree of arc suppression coil, the condition in resonant grounded power distribution system is more complicated than in ungrounded power system. Therefore the fault detection in a resonant grounded power distribution system is a tickler in indirectly earthed power system and the most existing methods used in field have the question which cannot find the faulty line accurately. On the basis of detailed analysis of the zero sequence measurement current distribution in resonant grounded power distribution system, a new detecting one-phase-to-ground fault feeder calculation method is proposed in this paper, which adds the arc suppressing coil compensation current to the zero sequence current of every feeders, is armed at the resonant grounded power distribution system and is based on the stable state analysis. EMPT simulation and analysis show that this calculation method has effectively raised the protecting abundant degree. The operation results of the power system indicated that the device which is developed in the calculation method has a high accuracy in the detecting fault feeder in the indirectly earthed power system regardless of running state including under compensation state, full compensation state and over compensation state.
引用
收藏
页码:61 / 65
相关论文
共 50 条
  • [1] Detecting single-phase-to-ground faulted feeder in resonant grounded power distribution system
    School of Information and Electrical Engineering, China University of Mining and Technology, Xuzhou 221008, China
    Zhongguo Kuangye Daxue Xuebao, 2006, 1 (104-108):
  • [2] Detecting Single-Phase-to-Ground Fault Event and Identifying Faulty Feeder in Neutral Ineffectively Grounded Distribution System
    Liu, Penghui
    Huang, Chun
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (05) : 2265 - 2273
  • [3] Protection for detecting single-phase-to-ground fault feeder based on synthesis increment principle in resonant grounded power distribution system with arc-suppression with magnetic bias
    Cai, Xu
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2003, 27 (20): : 68 - 72
  • [4] Detecting single-phase-to-ground fault feeder in compensation networks
    Tang, Yi
    Chen, Qing
    Liu, Hao
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2007, 31 (16): : 83 - 86
  • [5] Identifying single-phase-to-ground fault feeder in neutral noneffectively grounded distribution system using wavelet transform
    Dong, Xinzhou
    Shi, Shenxing
    IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) : 1829 - 1837
  • [6] Non-communication Protection for Single-Phase-to-Ground Fault Feeder in Neutral Non-Effectively Grounded Distribution System
    Jia, Qi
    Dong, Xinzhou
    Shi, Shenxing
    He, Xin
    2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2018,
  • [7] Protection and its application for detecting single phase earth fault feeder based on increment function principle in resonant grounded power distribution system
    Cai, Xu
    Yu, Yue-Zhong
    Shanghai Jiaotong Daxue Xuebao/Journal of Shanghai Jiaotong University, 2004, 38 (08): : 1273 - 1277
  • [8] Mathematical morphology-based single phase-to-ground fault feeder selector for a resonant grounded distribution system
    Han, X. L.
    Wu, Q. H.
    Li, M. S.
    Zhang, L. L.
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2018, 13 (03) : 517 - 518
  • [9] Study of detecting single-phase-to-ground fault feeder using a transient current direction
    School of Information and Electrical Engineering, China University of Mining and Technology, Xuzhou 221116, China
    Zhongguo Kuangye Daxue Xuebao, 2008, 2 (201-206):
  • [10] The Algorithm Research of Detecting Single-Phase-to-Ground Fault Line on Distribution Network with Distributed Generation
    Fan, Qiang
    Huang, Kai
    Xiao, Yong
    Xu, Mei-mei
    Chen, Jian-guo
    Gui, Wei
    2015 INTERNATIONAL CONFERENCE ON COMPUTER SCIENCE AND APPLICATIONS (CSA), 2015, : 99 - 104