Development of a new on-line monitoring device for distribution network lines

被引:0
|
作者
Tan W. [1 ]
Zhang W. [2 ]
Quan L. [3 ]
Chen Y. [1 ]
Song G. [2 ]
Zhang M. [1 ]
机构
[1] Zhuhai XJ Electric Co., Ltd., Zhuhai
[2] School of Electrical Engineering, Xi'an Jiaotong University, Xi'an
[3] State Grid Shaanxi Electric Power Research Institute, Xi'an
关键词
Distribution network; Model identification; On-line monitoring; Single-phase grounding fault; Synchronous recording;
D O I
10.7667/PSPC171867
中图分类号
学科分类号
摘要
In order to solve the problem that the traditional fault indicator in distribution network can't distinguish and locate the single-phase grounding fault in small current system, a model identification method based on transient zero sequence network is introduced, and a new on-line monitoring device for distribution network is developed. The three-phase probes obtain energy from the line to provide power for their own use through its self power module, use Roche coil to acquire the circuit, and measure voltage by the non-contact sensors, and realize the recording of fault waveform through distributed synchronous recording method based on short distance wireless communication. The communication terminal summarizes the fault waveforms and makes zero sequence vector synthesis. It automatically completes the identification and alarm instruction for single-phase grounding fault, and provides a new solution to solve the problem of the single-phase grounding fault location and improve the coverage rate of distribution network automation. The field experiment results show the practicability of the device and the accuracy of the detection and location of the single phase grounding fault in small current system. © 2019, Power System Protection and Control Press. All right reserved.
引用
下载
收藏
页码:158 / 165
页数:7
相关论文
共 20 条
  • [1] Yue R., Sun J., Design of new distribution network fault indicator, Electronic Device, 4, pp. 845-848, (2015)
  • [2] Xu Z., Analysis of factors affecting the accuracy of low current grounding line selection, Electric Power Science and Engineering, 31, pp. 93-97, (2015)
  • [3] Yang L., Shu Q., A new multiterminal detecting location method of single-phase grounding to the overhead-line for distribution network based on travelling-wave mutation of line-mode, Power System Protection and Control, 44, 9, pp. 22-28, (2016)
  • [4] Liu J., Zhang Z., Zhang X., Investigation on fault processing for electric power distribution networks, Power System Protection and Control, 45, 20, pp. 1-6, (2017)
  • [5] Xue H., Wang Z., Method of fault line selection based on zero sequence power, Power System Protection and Control, 36, 6, pp. 8-10, (2008)
  • [6] Zhan X., Hao S., Study of the signal injection method in indirectly earthed power system, Power System Protection and Control, 36, 6, (2008)
  • [7] Suonan J., Zhang C., Wang S., Suonan J., Zhang C., Wang S., Fault line selection in the non-solid earthed network based on the model identification method, Automation of Electric Power Systems, 28, 19, pp. 65-70, (2004)
  • [8] Liu J., Rui J., Zhang Z., Et al., Smart grounding power distribution systems, Power System Protection and Control, 46, 8, pp. 130-134, (2018)
  • [9] Yang J., Chang Z., Dou M., Et al., A frequency band adaptive acquisition method for single phase grounding line selection in distribution network, Power System Protection and Control, 43, 15, pp. 60-66, (2015)
  • [10] Li S., Song G., Kang X., Et al., Time-domain fault line selection based on correlation analysis in neutral indirect ground system, Power System Protection and Control, 36, 13, pp. 15-20, (2008)