Harmonic resonance characteristics of grid-connected system based on sensitivity theory

被引:0
|
作者
Wu J. [1 ]
Liu Z.-D. [1 ]
Wang C. [1 ]
Zhao J.-Q. [1 ]
You Y.-F. [1 ]
Xu D.-G. [1 ]
机构
[1] School of Electrical Engineering and Automation, Harbin Institute of Technology, Harbin
关键词
Grid-connected system; Participation of the network component; Resonance characteristic; Resonant circuit; Sensitivity analysis;
D O I
10.15938/j.emc.2018.12.002
中图分类号
学科分类号
摘要
In order to determine the network components which contributes significantly to a harmonic resonance phenomenon and composition of the resonant circuit, the sensitivity theory was applied to resonance characteristic analysis. Based on the modal analysis, the theory of sensitivity was applied to derive the solving formula for the sensitivities of each network component parameter under resonance circumstance, which reflects the participation of the network component. The solving formula was derived for parallel harmonic resonance and series harmonic resonance respectively. This solving formula was adapted to the 4-node grid-connected test system and the analysis result was obtained. Besides, the analysis results indicate that for certain frequency, the participation of parallel resonance and series resonance are not all the same. Finally, the results of simulation and experiment prove that the solving formula for sensitivity is feasible for grid-connected system. © 2018, Harbin University of Science and Technology Publication. All right reserved.
引用
收藏
页码:11 / 21and29
页数:2118
相关论文
共 20 条
  • [1] Xu D., Wang F., Ruan Y., Et al., Output impedance modeling of grid-connected inverters considering non-linear effects, Control and Modeling for Power Electronics, (2012)
  • [2] Hu W., Sun J., Ma Q., Et al., Resonant characteristics of multi-inverter grid-connection system, Electric Power Automation Equipment, 34, 7, (2014)
  • [3] Zhang X., Yu C., Liu F., Et al., Modeling and resonance analysis of multi-paralleled grid-tied inverters in PV systems, Proceedings of the CSEE, 34, 3, (2014)
  • [4] Yu C., Zhang X., Liu F., Et al., Modeling and resonance analysis of multi-parallel inverters system under asynchronous carriers conditions, IEEE Transactions on Power Electronics, 32, 4, (2017)
  • [5] Wang F., Feng X., Wu C., Et al., Research on grid harmonic interaction of multiple flyback micro-inverters, Proceedings of the CSEE, 36, 3, (2016)
  • [6] Hu W., Sun J., Ma Q., Et al., Analysis on interactive influences among multi grid-connected inverters, Power System Technology, 38, 9, (2014)
  • [7] Xiong X.-F., Zheng W., Chen K., Et al., Identification approach in modeling a photovoltaic grid-tie inverter, International Review of Electrical Engineering, 7, 3, (2012)
  • [8] Smith B.C., Arrillaga J., Wood A.R., Et al., A review of iterative harmonic analysis for AC-DC power systems, IEEE Transactions on Power Delivery, 13, 1, (1998)
  • [9] Borner A., Grebe T., IEEE harmonics model. Simulation task force modeling and simulation of the propagation of harmonics in electric power networks: Part I, IEEE Transactions on Power Delivery, 11, 1, (1996)
  • [10] Xu W., Zhang D., A modal analysis method for harmonic resonance assessment, Proceedings of the CSEE, 25, 22, (2005)