Research on atomization characteristics of high-pressure water mist atomizer for fire suppression

被引:0
|
作者
Fan, Minghao [1 ]
Zhou, Hua [1 ]
Yang, Huayong [1 ]
机构
[1] Zhejiang Univ., Hangzhou 310027, China
关键词
Atomization - Fire fighting equipment - Pressure - Simulation;
D O I
10.3901/jme.2002.09.017
中图分类号
学科分类号
摘要
High-pressure water mist system is a new type of fire-fighting unit using water hydraulic technology. The advantages of water mist include friendly environmental situation, fast and effective fire suppression, minimum quantity of water requirements and low water losses. It has been widely expected as the most potential substitute of Halon fire-fighting system. The inner flow state of the vital execute component - direct jet atomizer is analyzed by using the axial symmetrical boundary momentum integral method. The atomizer shape dimension's influence on two inner flow parameters, boundary layer thickness δ and accelerate factor K is assessed. Besides, the outer atomization characteristics related to fire-fighting performance, such as the outlet velocity and the Sauter Mean Diameter (SMD) are analyzed. Simulation results are experimentally verified. The results show that the system working pressure is the most important factor to those outer atomization characteristics and 8-9 MPa is the appropriate area of stable atomization pressure for this prototype of direct jet atomizer. The atomizer shape dimensions include contract angle α, and the length of atomizer neck l/d has influence on inner flow parameters and outer atomizer characteristics, but not distinct. The optimum atomizer's inner structure is selected.
引用
收藏
页码:17 / 21
相关论文
共 50 条
  • [1] Atomization parameters and fire suppression characteristics of water mist in simulated roadway
    Guo, Qing
    Ren, Wanxing
    GEOMATICS NATURAL HAZARDS & RISK, 2019, 10 (01) : 1529 - 1541
  • [2] Experimental Study on Fire Suppression of the Outdoor Oil-Immersed Transformer by High-Pressure Water Mist System
    Song, Huaitao
    Yao, Haowei
    Wei, Xiaoge
    Qin, Hengjie
    Li, Youxin
    Lv, Kefeng
    Chen, Qianlong
    FIRE-SWITZERLAND, 2023, 6 (06):
  • [3] Experimental study on fire suppression in ultrawide subsea immersed tube tunnels using high-pressure water mist
    Wang, Ziyang
    Wu, Peng
    Wu, Jun
    Shi, Xiaolong
    Lin, Gang
    Ji, Jie
    Qinghua Daxue Xuebao/Journal of Tsinghua University, 2025, 65 (04): : 697 - 706
  • [4] Characterization of an effervescent atomization water mist nozzle and its fire suppression tests
    Huang, X.
    Wang, X. S.
    Liao, G. X.
    PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2011, 33 : 2573 - 2579
  • [5] A high-pressure water mist system - Clean Fire Protection for Gas Turbines
    Voutilainen, Heikki
    Rohrbacher, D. I. Herbert
    Proceedings of the ASME Turbo Expo 2005, Vol 4, 2005, : 285 - 295
  • [6] Naval high pressure single-phase water mist fire suppression system
    The State Key Laboratory of Fluid Power Transmission and Control, Zhejiang University, Hangzhou 310027, China
    不详
    Binggong Xuebao, 2006, 4 (716-720):
  • [7] Suppression on the tunnel fire by coupling the longitudinal smoke discharge and high pressure water mist
    Zhang, P.-H. (zhangpeihong@mail.neu.edu.cn), 2013, Northeast University (34):
  • [8] NUMERICAL INVESTIGATION OF TWO-PHASE FLOW IN AN EFFERVESCENT ATOMIZER FOR WATER MIST FIRE SUPPRESSION
    Pan, Lingyong
    Yang, Gang
    Li, Baoren
    ATOMIZATION AND SPRAYS, 2011, 21 (10) : 819 - 831
  • [9] GEOMETRIC PRIMARY ATOMIZATION CHARACTERISTICS IN AN AIRBLAST ATOMIZER, HIGH PRESSURE CONDITIONS
    Fernandez, V. G.
    Lavergne, G.
    Berthoumieu, P.
    ATOMIZATION AND SPRAYS, 2011, 21 (01) : 17 - 29
  • [10] Progress in research and application of water mist fire suppression technology
    Liu, JH
    Liao, GX
    Li, PD
    Fan, WC
    Lu, Q
    CHINESE SCIENCE BULLETIN, 2003, 48 (08): : 718 - 725