Analysis of Long-term Measured Data of Audible Noise on UHV AC Double-circuit Transmission Lines on the Same Tower

被引:0
|
作者
Zhang Y. [1 ]
Li R. [2 ]
Zhou B. [1 ]
Liu Z. [1 ]
He W. [3 ]
Li B. [4 ]
机构
[1] State Key Laboratory of Power Grid Environmental Protection, Wuhan Branch of China Electric Power Research Institute, Wuhan
[2] State Grid Corporation of China, Beijing
[3] School of Electrical Engineering, Wuhan University, Wuhan
[4] State Grid DC Construction Company, Beijing
来源
关键词
1; 000; kV; Audible noise; BPA method; Double-circuit transmission lines on the same tower; Long-term measurement; UHV AC;
D O I
10.13336/j.1003-6520.hve.20170628027
中图分类号
学科分类号
摘要
In order to obtain the level and characteristics of audible noise from actual UHV AC double-circuit transmission lines on the same tower in operation, the long-term observation station for electromagnetic environment was established near 1 000 kV Huainan-Shanghai UHV AC double-circuit transmission lines on the same tower in Wuhu, Anhui Province. Typical spectra under different weather conditions and the of audible noise during rainy days were obtained for ten months. The results show that the data of audible noise during rainy days from the three measure points in Wuhu observation station conform to normal distribution, and the A-weighted level of audible noise and its 8 kHz components at 20 m away from the projection of outside phase have a good correlation. The L50 audible noise level during rainy days at 10 m and 20 m away from the projection of outside phase are 49.83 dB and 49.58 dB, respectively, which are in consistent with the calculation by using BPA method minus 2 dB. © 2017, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:2301 / 2308
页数:7
相关论文
共 26 条
  • [1] Liu Z., Innovation of UHVAC transmission technology in China, Power System Technology, 37, 3, pp. 1-8, (2013)
  • [2] Liu Z., Ultra-high Voltage AC & DC Grid, pp. 233-261, (2013)
  • [3] Technical guidelines for environmental impact assessment of electric power transmission and distribution project: HJ 24-2014, (2014)
  • [4] EPRI AC Transmission Line Reference Book-200 kV and Above, pp. 15-45, (2005)
  • [5] Liu Z., UHV AC Transmission Project Electromagnetic Environment, pp. 24-37, (2008)
  • [6] Sun X., Chen W., Lu J., Et al., Environmental Impact Assessment of AC Electric Power Transmission and Transformation Project, pp. 189-192, (2015)
  • [7] Juette G.W., Zaffanella L.E., Radio noise currents and audible noise on short sections of UHV bundles conductors, IEEE Transactions on Power Apparatus and Systems, 89, 5, pp. 902-913, (1970)
  • [8] Comber M.G., Zaffanella L.E., The use of single-phase overhead test lines and test cages to evaluate the corona effects of EHV and UHV transmission line, IEEE Transactions on Power Apparatus and Systems, 93, 1, pp. 81-90, (1974)
  • [9] Perry D.E., Chartier V.L., Reiner G.L., BPA 1 100 kV transmission system development corona and electric field studies, IEEE Transactions on Power Apparatus & Systems, 98, 5, pp. 1728-1738, (1979)
  • [10] Trinh N.G., Maruvada P.S., A method of predicting the corona performance of conductor bundles based on cage test results, IEEE Transactions on Power Apparatus and Systems, 98, 1, pp. 312-325, (1977)