An experimental study of the flow characteristics and velocity fields in an operating room with laminar airflow ventilation

被引:26
|
作者
Lin T. [1 ]
Zargar O.A. [1 ]
Lin K.-Y. [1 ]
Juiña O. [1 ]
Sabusap D.L. [1 ]
Hu S.-C. [1 ]
Leggett G. [2 ]
机构
[1] Department of Energy and Refrigerating Air-conditioning Engineering, National Taipei University of Technology, Taipei
[2] LI-COR Biosciences, Lincoln, NE
来源
Hu, Shih-Cheng (f10870@ntut.edu.tw) | 1600年 / Elsevier Ltd卷 / 29期
关键词
Ceiling return; Laminar airflow; Operating room; Smoke flow visualization; Ultra-clean ventilation;
D O I
10.1016/j.jobe.2020.101184
中图分类号
学科分类号
摘要
A critical aspect of the role of ventilation in hospital operating rooms (ORs) is the prevention of surgical site infection (SSI) which is largely attributable to airborne infection. Ventilation using clean filtered air is the primary means of airborne infection control. Many modern OR ventilation systems use laminar airflow (LAF) for air distribution. Conventional LAF ventilation supplies air directly over the surgical area which creates a sterile zone and uses wall-mounted air returns located at low level. A problem avoided with this design is the formation of recirculation in the non-sterile zone which arises due to disruption of LAF. This recirculation can lead to entrainment of the contaminated room air to the supply airflow which can increase the risk of SSI. In order to prevent this entrainment, airflow in the non-sterile zone has to be significantly altered. In this study, the application of ceiling returns and skirts in order to prevent the recirculation is experimentally investigated. Airflow patterns were analyzed using smoke flow visualization and particle image velocimetry (PIV). A novel laser sheet generator was used for illumination of the smoke particles. The effects of the supply flow rate, skirt length, and percentage of ceiling-return flow rate on the recirculation were assessed using Taguchi method. The results show that the application of ceiling return can eliminate the recirculation. Ceiling-return flow rate has the greatest influence, followed by the supply flow rate and the skirt. The findings of this study could contribute to the improvement of the conventional LAF ventilation design. © 2020
引用
收藏
相关论文
共 50 条
  • [1] A numerical investigation of vertical and horizontal laminar airflow ventilation in an operating room
    Sadrizadeh, Sasan
    Holmberg, Sture
    Tammelin, Ann
    BUILDING AND ENVIRONMENT, 2014, 82 : 517 - 525
  • [2] Numerical study of temperature-controlled airflow in comparison with turbulent mixing and laminar airflow for operating room ventilation
    Wang, Cong
    Holmberg, Sture
    Sadrizadeh, Sasan
    BUILDING AND ENVIRONMENT, 2018, 144 : 45 - 56
  • [3] The Effect of Airflow Velocity through a Laminar Airflow Ceiling (LAFC) on the Assessment of Thermal Comfort in the Operating Room
    Micko, Pavol
    Nosek, Radovan
    Hrabovsky, Peter
    Hecko, David
    APPLIED SCIENCES-BASEL, 2023, 13 (08):
  • [4] Laminar airflow and mixing ventilation: Which is better for operating room airflow distribution near an orthopedic surgical patient?
    Cao, Guangyu
    Nilssen, Anders M.
    Cheng, Zhu
    Stenstad, Liv-Inger
    Radtke, Andreas
    Skogas, Jan Gunnar
    AMERICAN JOURNAL OF INFECTION CONTROL, 2019, 47 (07) : 737 - 743
  • [5] EXPERIMENTAL LAMINAR-FLOW OPERATING-ROOM
    WHYTE, W
    SHAW, BH
    BARNES, R
    LANCET, 1971, 2 (7730): : 905 - &
  • [6] EXPERIMENTAL LAMINAR-FLOW OPERATING-ROOM
    SCOTT, CC
    LANCET, 1971, 2 (7734): : 1148 - &
  • [7] Experimental study of airflow characteristics of stratum ventilation in a multi-occupant room with comparison to mixing ventilation and displacement ventilation
    Cheng, Y.
    Lin, Z.
    INDOOR AIR, 2015, 25 (06) : 662 - 671
  • [8] Experimental and numerical study of room airflow under stratum ventilation
    Lin, Zhang
    Tian, Lin
    Yao, Ting
    Wang, Qiuwang
    Chow, T. T.
    BUILDING AND ENVIRONMENT, 2011, 46 (01) : 235 - 244
  • [9] Experimental measurements of surgical microenvironments in two operating rooms with laminar airflow and mixing ventilation systems
    Cao G.
    Kvammen I.
    Hatten T.A.S.
    Zhang Y.
    Stenstad L.-I.
    Kiss G.
    Skogås J.G.
    Energy and Built Environment, 2021, 2 (02): : 149 - 156
  • [10] Impact of surgical lights on the velocity distribution and airborne contamination level in an operating room with laminar airflow system
    Aganovic, Amar
    Cao, Guangyu
    Stenstad, Liv-Inger
    Skogas, Jan Gunnar
    BUILDING AND ENVIRONMENT, 2017, 126 : 42 - 53