Improvement and Application of Frequency Analysis Modules for Power System in High Proportion of Renewable Energy Situation

被引:0
|
作者
Gong H. [1 ]
Zhou Q. [1 ]
Guo Q. [1 ]
Qin X. [1 ]
Zhao S. [1 ]
Su L. [1 ]
He H. [1 ]
机构
[1] State Key Laboratory of Power Grid Safety and Energy Conservation (China Electric Power Research Institute), Haidian District, Beijing
来源
Gong, Haoyue (yjs-ghy@epri.sgcc.com.cn) | 1600年 / Power System Technology Press卷 / 45期
基金
中国国家自然科学基金;
关键词
High proportion of renewable energy; Primary frequency regulation; Simplified aggregation model; System frequency; System inertia;
D O I
10.13335/j.1000-3673.pst.2021.0672
中图分类号
学科分类号
摘要
By analyzing the existing frequency models of the systems with new energy, it is found that there exists a large margin of error under some certain conditions. By adding the limiting link of prime mover on the basis of the existing model, and distinguishing the proportion coefficient of effective adjustment and the proportion coefficient of effective inertia of the system, the frequency model and the simplified aggregation model of the new energy system with the limiting link are proposed. Typical system examples show that the two models have good fitting prediction effects under different new energy access proportions and different types. They can well reflect the overall inertia and the primary frequency regulation characteristics of the system. The actual power system example, which contains new energy and DC access, shows that the proposed simplified aggregation model can accurately reflect the frequency variation of the power system and has engineering application values. © 2021, Power System Technology Press. All right reserved.
引用
收藏
页码:4603 / 4611
页数:8
相关论文
共 22 条
  • [1] ZHOU Xiaoxin, CHEN Shuyong, LU Zongxiang, Et al., Technology features of the new generation power system in China, Proceedings of the CSEE, 38, 7, pp. 1893-1904, (2018)
  • [2] SHEN Hong, ZHOU Qinyong, LIU Yao, Et al., Key technologies and prospects for the construction of global energy internet under the background of carbon neutral, Power Generation Technology, 42, 1, pp. 8-19, (2021)
  • [3] 35, (2020)
  • [4] (2016)
  • [5] (2015)
  • [6] KUNDUR P, BALU N J, LAUBY M G., Power system stability and control, (1994)
  • [7] ANDERSON P M, MIRHEYDAR M., A low-order system frequency response model, IEEE Transactions on Power Systems, 5, 3, pp. 720-729, (1990)
  • [8] LIU Fusuo, QING Mengqi, TANG Fei, Et al., Limit proportion calculation of wind power considering primary frequency modulation and frequency constraints, Power System Technology, 45, 3, pp. 863-870, (2021)
  • [9] ZHENG Chao, WANG Shiyuan, ZHANG Boqi, Et al., Dynamic frequency characteristics and countermeasures of power grid with highly penetrated photovoltaics, Power System Technology, 43, 11, pp. 4064-4073, (2019)
  • [10] SUN Huadong, WANG Baocai, LI Wenfeng, Et al., Research on inertia system of frequency response for power system with high penetration electronics, Proceedings of the CSEE, 40, 16, pp. 5179-5191, (2020)