Research on cross-interval maintenance technology of intelligent substation based on SCD and CCD calibration

被引:0
|
作者
Yang G. [1 ]
Xie B. [1 ]
Zeng Z. [1 ]
Zou G. [1 ]
Feng Z. [2 ]
机构
[1] State Grid Chongqing Electric Power Company City Power Supply Branch, Chongqing
[2] PONOVO Power CO., LTD, Beijing
关键词
Closed loop automatic test; Cross-interval overhaul; Intelligent substation; Substation configuration descriptions file (SCD); Synchronous output;
D O I
10.7667/PSPC180054
中图分类号
学科分类号
摘要
To address the problem of heavy distributed debugging workload and communication failure of virtual terminal loop in intelligent substation secondary protection equipment, a cross-interval maintenance system based on SCD file and CCD file calibration is introduced. The system is mainly composed of consistency ratio and synchronous control detection. Based on the correct result of consistency comparison between the SCD file and the CCD file, this paper makes nine sets of power amplifiers output synchronously at most by using the theory of optical clock synchronization. Each power amplifier can output three phase voltage and three phase current and re-collect intelligent terminal protection tripping signals through hard contact of eight-way switch of power amplifier to realize one-time closed loop maintenance test of multi-spacing protection, for example main transformer, line, etc. Intelligent substation cross-interval maintenance system based on SCD file and CCD file calibration realizes multi-interval integral test of secondary equipment in intelligent substation, which has certain reference value for improving debugging and maintenance efficiency of intelligent substation and carrying out automatic test of the whole station. © 2019, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:175 / 181
页数:6
相关论文
共 24 条
  • [1] Huang Y., Intelligent substation is the development goal of substation integration automation, Power System Protection and Control, 41, 2, pp. 45-48, (2013)
  • [2] Hu B., Guo Y., Yang B., Et al., Research on status and development trend of smart substation technology, Smart Power, 46, 3, pp. 87-90, (2018)
  • [3] Bo Z.Q., Lin X.N., Wang Q.P., Et al., Developments of power system protection and control, Protection and Control of Modern Power Systems, 1, 1, pp. 1-8, (2016)
  • [4] Luo P., Hao X., Zhao Y., Et al., Research on integrated testing technology of secondary equipment in smart substation based on wireless communication, Electrical Measurement & Instrumentation, 54, 2, pp. 76-82, (2017)
  • [5] Gao L., Bu Q., Yuan Y., Et al., Smart substation commissioning and safety measures based on secondary circuit comparison, Automation of Electric Power Systems, 39, 20, pp. 130-134, (2015)
  • [6] Ye Y., Sun Y., Huang T., Et al., Online state detection and fault diagnosis technology of relay protection secondary circuits in smart substation, Power System Protection and Control, 44, 20, pp. 148-153, (2016)
  • [7] Yang Y., Gao X., Zhu H., Et al., Case study on SCD application based on demo smart substation, Power System Protection and Control, 43, 22, pp. 107-113, (2015)
  • [8] He X., Li J., Chen J., Et al., Construction scheme study on configuration file management and control system in intelligent substation, Smart Power, 45, 8, pp. 75-81, (2017)
  • [9] Huang Z., Li Y., Li T., Et al., Design and implementation of automatic generation technology of SCD file virtual circuit in smart substation, Power System Protection and Control, 45, 17, pp. 106-111, (2017)
  • [10] Liu X., Han Z., Li Y., Application research of relationship between GOOSE message and SCD files, Power System Protection and Control, 41, 24, pp. 95-100, (2013)