Partial Discharge Characteristics of DC Electrical Tree in XLPE During Voltage Drop

被引:0
|
作者
Lin G. [1 ]
Zhang H. [1 ]
Zheng Z. [1 ]
Wang Y. [1 ]
Zhou M. [2 ]
Yin Y. [1 ]
机构
[1] Department of Electrical Engineering, Shanghai Jiao Tong University, Shanghai
[2] Global Energy Interconnection Research Institute Europe GmbH, Berlin
来源
关键词
DC electrical tree; insulation diagnosis; partial discharge; space charge; XLPE;
D O I
10.13336/j.1003-6520.hve.20221932
中图分类号
学科分类号
摘要
The electrical tree is a typical defect of XLPE HVDC cables. Effective detection of the tree is of vital importance for the evaluation of cable insulation status. In this paper, DC partial discharge (PD) experiments were carried out on the XLPE insulation samples with electrical trees. The characteristics of PD at different stages and voltage parameters were analyzed. It is found that PD occurs in the samples with electrical tree defects during the DC voltage drop, while the samples without electrical trees have no PD. The polarity of the PD during the voltage drop is opposite to that in the constant voltage stage. The PD shows good repeatability and has a negligible effect on the tree size. The experiment shows that the PD detection in the voltage drop stage can provide a reference for the evaluation of the electrical tree of HVDC cables. In addition, the experiment shows that multiple PD may lead to the increase of tree conductivity and PD extinction voltage. The experimental results of different voltage parameters show that higher DC voltage and appropriate voltage reduction rate can increase the PD number. The average PD amplitude is higher when the needle electrode suffers negative voltage. Constant voltage duration time has a negligible effect on PD characteristics. Numerical simulation was used to analyze the electric field in the insulation during the voltage drop. The study shows that the attenuation rate of the Poisson electric field is lower than that of the applied electric field in the early stage, which results in the formation of a reverse electric field with high intensity around the needle tip, thus resulting in PD during the voltage drop. © 2024 Science Press. All rights reserved.
引用
收藏
页码:348 / 358
页数:10
相关论文
共 30 条
  • [1] DU Boxue, LI Zhonglei, YANG Zhuoran, Et al., Application and research progress of HVDC XLPE cables, High Voltage Engineering, 43, 2, pp. 344-354, (2017)
  • [2] CHEN Zhengzheng, ZHAO Peng, LI Zhenyu, Et al., Effective method for evaluating the electrical properties of DC cable insulation materials, High Voltage Engineering, 47, 10, pp. 3558-3565, (2021)
  • [3] LIU Ying, ZHANG Bojian, GAO Xin, Establishment and application of a comprehensive system for condition assessment of HV XLPE cable lines, High Voltage Engineering, 48, 11, pp. 4437-4444, (2022)
  • [4] ISHIBASHI A, KAWAI T, NAKAGAWA S, Et al., A study of treeing phenomena in the development of insulation for 500 kV XLPE cables, IEEE Transactions on Dielectrics and Electrical Insulation, 5, 5, pp. 695-706, (1998)
  • [5] GUO Feng, WANG Yani, LE Yanjie, Et al., Temperature characteristics of periodically grounded DC tree and AC tree in XLPE and MgO/XLPE Nano-composite insulation, High Voltage Engineering, 44, 5, pp. 1459-1466, (2018)
  • [6] LI Shengtao, ZHENG Xiaoquan, Electrical treeing in polymers, pp. 196-205, (2006)
  • [7] LIU Ying, CAO Xiaolong, Growth characteristics of electrical trees in XLPE cable insulation under DC voltage, Journal of Xi’an Jiaotong University, 48, 4, pp. 41-46, (2014)
  • [8] HAMMARSTROM T J A, BENGTSSON T, GUBANSKI S M., Partial discharge characteristics of electrical treeing in XLPE insulation exposed to voltages of different rise times, Proceedings of 2017 International Symposium on Electrical Insulating Materials, pp. 407-410, (2017)
  • [9] ZHU X, WU J D, WANG Y L, Et al., Characteristics of electrical tree defect during the growth period in high-voltage DC cable under stepped DC voltage, IET Generation, Transmission & Distribution, 13, 15, pp. 3195-3201, (2019)
  • [10] LI Yanda, Electrical tree initiation and growth properties in HVDC cables, pp. 38-39, (2019)