Multi-port Inductively Coupled HVDC Current Limiting Circuit Breaker

被引:0
|
作者
Li G. [1 ]
Wang W. [1 ]
He Z. [2 ]
Xin Y. [1 ]
Gu H. [2 ]
机构
[1] School of Electrical Engineering, Northeast Electric Power University, Jilin, 132012, Jilin Province
[2] Global Energy Interconnection Research Institute Co., Ltd., Changping District, Beijing
来源
基金
中国国家自然科学基金;
关键词
Coupled inductance; Current limiting circuit breaker; Economy; Multi-port DC power grid;
D O I
10.13335/j.1000-3673.pst.2019.2197
中图分类号
学科分类号
摘要
The grounding fault of DC power grid will lead to converter blockade, fault area expanding. The configuration of DC current limiter and DC circuit breaker is a general solution to the above problem. In this paper, a multi-port DC current limiting circuit breaker is designed for HVDC power grid with two sets of coupled inductors. This equipment consists of three parts: primary current limiter, fault isolation current limiter and drainage branch. The former two parts are connected in series in each line of the same DC bus, and the drainage branch is the common part of each DC line. The switching devices of the different parts can improve their economy by cooperating with each other and borrowing from each other. A model of Zhangbei four-terminal DC power grid is built on PSCAD simulation software and compared with several other existing schemes. The results show that the current limiting circuit breaker proposed in this paper can complete the relevant actions of power electronic devices within 6ms with low impact voltage to each switch group. If it is applied to N-port DC bus, only (26n+502) switch groups are needed, which has high economy. © 2020, Power System Technology Press. All right reserved.
引用
收藏
页码:3866 / 3874
页数:8
相关论文
共 19 条
  • [1] Xin Yechun, Wang Weiru, Li Guoqing, Et al., A power hardware-in-loop simulation for MMC-MTDC transmission systems, Power System Technology, 42, 12, pp. 3903-3909, (2018)
  • [2] Li Guoqing, Wang Weiru, Xin Yechun, Et al., Sub-module grouping modulation strategy of modular multilevel converter, High Voltage Engineering, 44, 7, pp. 2107-2114, (2018)
  • [3] Xin Yechun, Wang Weiru, Li Guoqing, Et al., Control strategy of modular multilevel converter based on arm current direct control, Electric Power Automation Equipment, 38, 10, pp. 115-120, (2018)
  • [4] Yan Xiao, Jiao Yanjun, Du Zhe, Feasibility study of AC/DC hybrid distribution network using VSC-based DC technology, Power System Protection and Control, 45, 13, pp. 110-116, (2017)
  • [5] Lu Zhengfei, Cai Yijun, Liu Zijun, Et al., A line break fault protection algorithm for high voltage overhead line based on two-terminal information, Power System Protection and Control, 46, 20, pp. 39-45, (2018)
  • [6] Zhang Xiangyu, Yu Zhanqing, Huang Yulong, Et al., Principle and development of 500kV hybrid DC circuit breaker based on coupled negative voltage commutation, Journal of Global Energy Interconnection, 1, 4, pp. 413-422, (2018)
  • [7] Li Chengyu, Zhao Chengyong, Xu Jianzhong, Et al., A pole-to-pole short-circuit fault current calculation method for DC grids, IEEE Transactions on Power Systems, 32, 6, pp. 4943-4953, (2017)
  • [8] Gao Yang, He Zhiyuan, Wang Chenghao, Et al., A new hybrid circuit breaker for DC-application, Power System Technology, 40, 5, pp. 1320-1325, (2016)
  • [9] Guan Eryong, Dong Xinzhou, Feng Teng, A solid DC current limiter topology, Proceedings of the CSEE, 37, 4, pp. 978-986, (2017)