Study on the collapse failure of transmission tower-line system under downburst

被引:0
|
作者
Bi W.-Z. [1 ]
Tian L. [1 ]
机构
[1] School of Civil Engineering, Shandong University, Jinan
来源
关键词
Collapse failure; Downburst; Finite element simulation; Response history analysis; Transmission tower-line system;
D O I
10.6052/j.issn.1000-4750.2021.05.S012
中图分类号
学科分类号
摘要
The short-term destructive strong wind formed by the downburst near the ground will pose a greater threat to building structures, especially to wind-sensitive structures such as transmission tower-line systems. Based on practical engineering, a new finite element model for the transmission tower-line system is established. The deterministic-stochastic hybrid model is used to simulate the generation of the downburst wind field. Based on the Tian-Ma-Qu material model, the progressive collapse process of the structure under the downburst is conducted. The research results demonstrate that: the transmission tower under the downburst performs its significant local deformation in a short time, the buckling of many diagonal members and several main members is the governing reason for the entire collapse of the tower. The segment 6 of the tower is considered the weakest position, to which should be particularly paid attention in the design of the structural resistance to downburst. Copyright ©2022 Engineering Mechanics. All rights reserved.
引用
收藏
页码:78 / 83
页数:5
相关论文
共 18 条
  • [1] Liu Muguang, Wang Shubin, Xie Zhuangning, Et al., Equivalent static wind load of transmission tower based on displacement measurement, Engineering Mechanics, 34, 4, pp. 160-166, (2017)
  • [2] Liu Juncai, Tian Li, Zhang Rui, Et al., Study on the prediction of the most adverse input direction of transmission tower-line system under far-field seismic ground motions, Engineering Mechanics, 37, 1, pp. 97-103, (2020)
  • [3] Dempsey D, White H B., Winds wreak havoc on lines, Transmission & Distribution World, 48, 6, pp. 32-37, (1996)
  • [4] Xie Qiang, Zhang Yong, Li Jie, Investigation on tower collapse of 500 kV Renshang 5237 transmission line caused by downburst, Power System Technology, 30, 10, pp. 59-63, (2006)
  • [5] Fu D, Yang F, Li Q, Et al., Simulations for tower collapses of 500kV Zhengxiang transmission line induced by the downburst, 2010 International Conference on Power System Technology: Technological Innovations Making Power Grid Smarter, (2010)
  • [6] Yao Dan, Shen Guohui, Pan Feng, Et al., Wind-induced dynamic response of transmission tower using vector-form intrinsic finite element method, Engineering Mechanics, 32, 11, pp. 63-70, (2015)
  • [7] Shehata A Y, Damatty A, Savory E., Finite element modeling of transmission line under downburst wind loading, Finite Elements in Analysis & Design, 42, 1, pp. 71-89, (2006)
  • [8] Shehata A Y, Damatty A., Failure analysis of a transmission tower during a microburst, Wind & Structures an International Journal, 11, 3, pp. 193-208, (2008)
  • [9] Savory E, Parke G, Zeinoddini M., Modelling of tornado and microburst-induced wind loading and failure of a lattice transmission tower, Engineering Structures, 23, 4, pp. 365-375, (2001)
  • [10] Damatty A E, Elawady A., Critical load cases for lattice transmission line structures subjected to downbursts: Economic implications for design of transmission lines, Engineering Structures, 159, 15, pp. 213-226, (2018)