Quantitative Analysis of System Strength of Renewable Energy Generation Grid-connected System Based on Transient Overvoltage Constraint

被引:0
|
作者
Sun H. [1 ]
Yu L. [1 ]
Zhao B. [1 ]
机构
[1] State Key Laboratory of Power Grid Safety and Energy Conservation (China Electric Power Research Institute), Haidian District, Beijing
关键词
grid-connected scale; power system with renewable energy; short- circuit capacity; tansient overvoltage; voltage support strength;
D O I
10.13334/j.0258-8013.pcsee.220468
中图分类号
学科分类号
摘要
The strength of system with renewable energy generation (REG) has an important impact on the severity of transient overvoltage. A quantification method is proposed by using the short-circuit ratio (SCR) as the system strength index and considering the interaction in multi-infeed systems. First, the relationship is analyzed among the voltage, reactive power, and short-circuit capacity at the transient overvoltage moment. Furthermore, the interaction in multi-infeed systems is analyzed by using voltage phase method, and the mathematical model for multi-infeed system is established. The correlation between the system strength and the transient overvoltage is analyzed by combining SCR and this model. Meanwhile, a quantitative method of REG maximum scale is proposed by taking 1.3pu as the constraint due to the transient overvoltage, and the calculation method of minimum short-circuit capacity is proposed to improve system strength. Finally, the correlation between system strength and transient overvoltage is verified by examples. ©2023 Chin.Soc.for Elec.Eng.
引用
收藏
页码:4207 / 4217
页数:10
相关论文
共 24 条
  • [1] SUN Dawei, WU Linlin, LIU Hui, Effect of the low voltage ride through characteristics on PMSG terminal transient voltage in weakly-synchronized gird[J], Proceedings of the CSEE, 41, 14, pp. 4777-4786, (2021)
  • [2] YANG Shuo, WANG Weisheng, LIU Chun, Dynamic voltage security analysis and control strategy for wind power centralized system[J], High Voltage Engineering, 43, 6, pp. 2080-2087, (2017)
  • [3] YIN Yue, LIU Tianqi, DING Lijie, Security and stability analysis method for weak sending-end system under commutation failure based on improved risk assessment[J], Power System Technology, 44, 6, pp. 2177-2186, (2020)
  • [4] WU Ping, CHEN Hao, ZHAO Bing, Study on interaction and stability characteristics of bundled wind-PV-thermal power transmitted with AC/DC system[J], Power System Technology, 40, 7, pp. 1934-1942, (2016)
  • [5] HAN Pingping, ZHANG Haitian, DING Ming, A coordinated HVRT strategy of large-scale wind power transmitted with HVDC system[J], Power System Technology, 42, 4, pp. 1086-1092, (2018)
  • [6] CHOOPANI M, HOSSEINIAN S H,, VAHIDI B., New transient stability and LVRT improvement of multi-VSG grids using the frequency of the center of inertia[J], IEEE Transactions on Power Systems, 35, 1, pp. 527-538, (2020)
  • [7] CHANG Yuanzhu, Jiabing HU, TANG W, Fault Current analysis of type-3 WTs considering sequential switching of internal control and protection circuits in multi time scales during LVRT[J], IEEE Transactions on Power Systems, 33, 6, pp. 6894-6903, (2018)
  • [8] JIA Junchuan, JIN Yiding, ZHAO Bing, Impact analysis and performance optimization of LVRT control of wind turbine on transient overvoltage of power system[J], Power System Technology, 45, 2, pp. 526-533, (2021)
  • [9] TU Jingzhe, ZHANG Jian, LIU Mingsong, Study on wind turbine generators tripping caused by HVDC contingencies of wind-thermal-bundled HVDC transmission systems[J], Power System Technology, 39, 12, pp. 3333-3338, (2015)
  • [10] TU Jingzhe, ZHANG Jian, LIU Mingsong, Mechanism analysis of transient overvoltage with large disturbance considering dynamic characteristics of wind generator[J], Automation of Electric Power Systems, 44, 11, pp. 197-205, (2020)