Synchronous Control Strategy of Parallel Contactor Based on Single-pole Switch

被引:0
|
作者
Zhang B. [1 ]
Xu Z. [1 ]
机构
[1] Fujian Province Key Laboratory of New Energy Generation and Power Conversion, School of Electrical Engineering, Fuzhou University, Fuzhou, 350116, Fujian Province
基金
中国国家自然科学基金;
关键词
Parallel contactor; Self-adaptive; Single-pole switch; Synchronous control; Zero current breaking;
D O I
10.13334/j.0258-8013.pcsee.191855
中图分类号
学科分类号
摘要
The contacts of contactor are connected in parallel to form a parallel contactor to realize capacity expansion operation, because the contact systems are independent of each other, it is difficult to guarantee the synchronicity of the close and break process and the stability of the holding process. Therefore, this paper proposed a synchronous control strategy based on single-pole switch: through logical processing of coil control signal of each contactor, the independent contact system of each single pole switch was controlled by correlation, so as to realize the synchronism fixed-phase closing action of each pole contactor and zero-current closing action. By detecting the current transfer phenomenon in the breaking process of the parallel contactor, the breaking sequence and breaking time were identified online, and the breaking sequence was dynamically adjusted; Following the change of breaking time of contactor, the breaking time was adaptively adjusted in the set zero-current breaking region. In the holding process, in order to prevent asynchronous malfunction, normal and abnormal coil current control modes were designed. Took the working condition of contact as the feedback adaptive adjusting coil current control mode, which changes the single energy-saving operation control mode in which the coil current remains unchanged during the holding process, and realize adaptive synchronous stable holding of parallel contactors. Related experiments verify the effectiveness of the control strategy. © 2020 Chin. Soc. for Elec. Eng.
引用
收藏
页码:5352 / 5362
页数:10
相关论文
共 23 条
  • [1] Xu Zhihong, Electrical theory basis, (2014)
  • [2] Bai Qingsheng, Yuan Yan, GSC2-1250F high current AC contactor design, Mechanical Research & Application, 3, pp. 116-118, (2010)
  • [3] Ge Guowei, Investigation on synergy and arc control characteristics of series-connected vacuum arcs in multi-break VCBs, (2017)
  • [4] Yin Ting, Chen Xuanshu, Du Yan, Et al., Design of large-capacity high-voltage breakers using tightly-coupled reactor, High Voltage Engineering, 36, 6, pp. 1577-1582, (2010)
  • [5] Niu Chenxu, Lyu Meng, Zheng Xiang, Simulation analysis on break structure of paralleled vacuum circuit breaker, Journal of Dalian Jiaotong University, 35, S1, pp. 114-118, (2014)
  • [6] Lin Lijie, Zhao Xiaoyun, Liu Bingzhang, FYJC 5-2000 type of AC contactor with expended capacity in parallel, Low Voltage Apparatus, 3, pp. 38-40, (2003)
  • [7] Xu Zhihong, Zhang Peimin, Research on dynamic closing course of intelligent AC contactor, Proceedings of the CSEE, 27, 18, pp. 108-113, (2007)
  • [8] Alexander R W., Synchronous closing control for shunt capacitors[J], IEEE Transactions On Power Apparatus and Systems, PAS-104, 9, pp. 2619-2626, (1985)
  • [9] Lee W Y, Park K Y, Chong J K, Et al., A method to decide the switching instants of controlled switching circuit breaker for shunt reactors[C], Proceedings of IEEE/PES Transmission and Distribution Conference and Exhibition, pp. 1760-1765, (2002)
  • [10] Wang Yang, Xu Zhihong, Inrush current suppression strategy of three-phase transformer based on combined-switches, Electric Power Automation Equipment, 39, 7, pp. 99-106, (2019)