Fault analysis method for a power line based on instantaneous phase consistency

被引:0
|
作者
Luo J. [1 ]
Jiang L. [1 ]
Cui Q. [1 ]
Zhong J. [2 ]
Zhang L. [2 ]
机构
[1] School of Electrical Engineering, Chongqing University, Chongqing
[2] State Grid Chongqing Electric Power Company Research Institute, Chongqing
基金
中国国家自然科学基金;
关键词
fault analysis; fault location; instantaneous phase consistency; power line; transition impedance calculation;
D O I
10.19783/j.cnki.pspc.230472
中图分类号
学科分类号
摘要
With the construction of the new power system, it is becoming increasingly difficult to obtain the steady-state component of a fault. Therefore, a power line fault analysis method based on instantaneous phase consistency using fault transient data is proposed. First, the transient data of fault current and voltage at both ends of the line are represented by a sinusoidal function, and the electrical quantity along the line is calculated. Then, according to the condition of instantaneous phase consistency of the calculated voltage at both ends of the fault point, a criterion function is constructed to determine the fault location. The general situation is that the transition impedance of the grounding fault is not pure resistance and the transition resistance of each phase of the polyphase grounding fault is not equal. Considering three kinds of ground short-circuit faults, the transient impedance parameters of the fault point are calculated using the condition of instantaneous phase consistency of voltage and current on the transition resistance. Through the analysis of simulation cases and actual field cases, and compared with other fault location methods, the fault location accuracy of the proposed method for calculating instantaneous phase consistency of voltage is significantly improved, and it has stronger applicability. From the effect of instantaneous phase consistency of voltage and current on the transition resistance, different types of fault transition impedance parameters can be effectively calculated. © 2023 Power System Protection and Control Press. All rights reserved.
引用
收藏
页码:178 / 186
页数:8
相关论文
共 28 条
  • [1] STANOJEVIC V A, PRESTON G, TERZIJA V., Synchronised measurements based algorithm for long transmission line fault analysis, IEEE Transactions on Smart Grid, 9, 5, pp. 4448-4457, (2018)
  • [2] SUN Zichang, DENG Yingjun, CHEN Hao, Et al., Analysis of homogeneous phase cross-country faults of double-circuit lines on the same tower, Power System Protection and Control, 49, 4, pp. 154-159, (2021)
  • [3] WANG Yan, LIU Meicen, CHEN Xu, Et al., Fault analysis of mixed-voltage double-circuit lines partly on same tower under different grounding modes of neutral point, Electric Power Automation Equipment, 38, 10, pp. 159-165, (2018)
  • [4] WU Jianwei, SHAO Jianfeng, Fault location of DC transmission lines based on backward waves considering wave speed changes, Electric Power, 54, 5, pp. 121-128, (2021)
  • [5] ZHANG Zhuangzhuang, ZHU Lingyu, WANG Leilei, Et al., Test study on influence of load factors on vibration and noise characteristics of the three-phase oil immersed transformer under new power system, High Voltage Apparatus, 58, 9, pp. 45-54, (2022)
  • [6] LI Huiling, WANG Xi, GAO Jian, Et al., Scheme construction for sending end dc grids in western China under the background of new power system, Electric Power, 56, 5, pp. 12-21, (2023)
  • [7] BILGUNDI S K, SACHIN R, PRADEEPA H, Et al., Grid power quality enhancement using an ANFIS optimized PI controller for DG, Protection and Control of Modern Power Systems, 7, 1, pp. 26-39, (2022)
  • [8] WU Chengguo, XIAO Shiwu, ZHU Jian, Calculation of power grid partition short-circuit current with negative sequence voltage-supported distributed generation, Power System Technology, 47, 3, pp. 1159-1169, (2023)
  • [9] LI B, LIAO K, YANG J W, Et al., Transient fault analysis method for VSC-based DC distribution networks with multi-DGs, IEEE Transactions on Industrial Informatics, 18, 11, pp. 7628-7638, (2022)
  • [10] LIU Xiaolin, CAO Zeyu, GAO Bingtuan, Et al., Evaluation index of transient overvoltage during fault at HVDC sending-end AC system, Electric Power Construction, 44, 1, pp. 64-72, (2023)