SDIM-ITM interface algorithm and time delay compensation for a power hardware-in-the-loop simulation of MMC-HVDC

被引:0
|
作者
Li G. [1 ]
Wang Y. [1 ]
Xiong Y. [2 ]
机构
[1] School of Electrical Engineering, Northeast Electric Power University, Jilin
[2] Beijing Jingxi Gas-fired Thermal Power Corporation, Beijing
关键词
MMC-HVDC; PHIL; SDIM-ITM interface; Simulation accuracy; Time delay compensation;
D O I
10.7667/PSPC180162
中图分类号
学科分类号
摘要
To deal with the accuracy problem of Power Hardware-In-the-Loop (PHIL) simulation for Modular Multilevel Converter-based HVDC (MMC-HVDC) caused by the power interface hardware, a phase-lead correction unit that simulates an first-order high-pass RC filter is designed for time delay compensation. In this paper, the MMC is modeled with Thevenin's equivalent circuit to derive the real time value of damping impedance for SDIM interface and reduce the calculation burden. The SDIM-ITM interface is adopted for MMC-HVDC PHIL simulation, where ITM interface acts as a driver and SDIM interface acts as an observer, and it shows high accuracy and stability under conditions of both change of operating point and fault. However, the physical simulation accuracy is influenced by the interface (or power amplifier) time delay. Thus the phase of AC voltage signal exciting power amplifier is compensated by the proposed phase-lead correction unit to further improve the physical simulation accuracy. The effectiveness of the proposed time delay compensation method is verified by simulation results. © 2019, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:56 / 63
页数:7
相关论文
共 21 条
  • [1] Cai Y., Ren C., Zhou J., Et al., Control strategy for suppressing capacitor voltage ripple of MMC-HVDC, Power System Protection and Control, 45, 5, pp. 45-50, (2017)
  • [2] Liu S., Xu D., Mei N., Et al., Research on the effect of DC side fault on modular multilevel converter, Power System Protection and Control, 45, 10, pp. 48-54, (2017)
  • [3] Xu Y., Luo Y., Shi T., Et al., A new MMC sub-module with DC fault self-clearing ability and its hybrid topology, Power System Protection and Control, 46, 7, pp. 129-137, (2018)
  • [4] Zeng F., Yue K., Han T., Voltage-sharing control strategy for mmc low switching frequence sub-modele, Guangdong Electric Power, 31, 6, pp. 99-106, (2018)
  • [5] Zhang X., Zhao C., Pang H., Et al., A control and protection scheme of multi-terminal DC transmission system based on MMC for DC line fault, Automation of Electric Power Systems, 37, 15, pp. 140-145, (2013)
  • [6] Liu D., Tang G., He Z., Et al., Hybrid real-time simulation technology for MMC-HVDC, Electric Power Automation Equipment, 33, 2, pp. 68-73, (2013)
  • [7] Zhou J., Guo J., Hu T., Et al., Digital/analog dynamic simulation for ±500 kV HVDC transmission system, Transactions of China Electrotechnical Society, 27, 5, pp. 221-228, (2012)
  • [8] Dione M., Sirois F., Bonnard C.H., Evaluation of the impact of superconducting fault current limiters on power system network protections using a RTS-PHIL methodology, IEEE Transactions on Applied Puperconductivity, 21, 3, pp. 2193-2196, (2011)
  • [9] Ren W., Sloderbeck M., Interfacing issues in real-time digital simulators, IEEE Transactions on Power Delivery, 26, 2, pp. 1221-1230, (2011)
  • [10] Ren W., Steurer M., Baldwint L., Improve the stability and the accuracy of Power Hardware-in-the-Loop simulation by selecting appropriate interface algorithms, IEEE Transactions on Industry Applications, 44, 4, pp. 1286-1294, (2008)