Subsynchronous Oscillation Early Warning Method for Wind Farm Integration Grid System Based on Graph Attention Network

被引:0
|
作者
Wang Y. [1 ]
Wu H. [1 ]
Yu G. [2 ]
Yin A. [2 ]
Zheng Z. [1 ]
Liao J.
机构
[1] College of Electrical Engineering, Sichuan University, Chengdu
[2] Jinan Power Supply Company, State Grid Shandong Electric Power Company, Jinan
来源
关键词
deep learning; multi-head graph attention network; oscillation early warning; subsynchronous oscillation; wind farm grid injection;
D O I
10.13336/j.1003-6520.hve.20221459
中图分类号
学科分类号
摘要
Large-scale doubly-fed wind farms which are connected to the power grid through series capacitor compensation can easily lead to subsynchronous oscillation of the power system. If the oscillation phenomenon can not be timely detected to give an accurate alarm, it will seriously threaten the safe and stable operation of the system. The subsynchronous oscillation early warning is based on the online measurement data of the power system to judge the stability of the system oscillation and provide real-time and reliable early warning information for dispatchers. In order to solve the problem that the existing online monitoring of subsynchronous oscillation cannot realize pre-warning, this paper proposes a subsynchronous oscillation early warning method based on graph attention network (GAT). First, the key influencing factors of secondary synchronous oscillation are screened from the wind farm side and the grid side, respectively, to reduce the redundancy of input feature information. Secondly, based on the multi-head attention mechanism, a multi-head attention network is constructed to realize the aggregation of sub-synchronous oscillation characteristics among different wind farms after considering the differences in the coupling effects between different wind farms and between wind farms and the power grid. Finally, the subsynchronous oscillation stability early warning is carried out on the multi-wind farm integrated grid system, and the accuracy and anti-interference of the method proposed in this paper are verified. © 2023 Science Press. All rights reserved.
引用
收藏
页码:2995 / 3005
页数:10
相关论文
共 28 条
  • [1] MA Ningning, XIE Xiaorong, HE Jingbo, Et al., Review of wide-band oscillation in renewable and power electronics highly integrated power systems, Proceedings of the CSEE, 40, 15, pp. 4720-4731, (2020)
  • [2] GUO Chuangxin, LIU Zhuping, FENG Bin, Et al., Research status and prospect of new-type power system risk assessment, High Voltage Engineering, 48, 9, pp. 3394-3404, (2022)
  • [3] DONG Xiaoliang, TIAN Xu, ZHANG Yong, Et al., Practical SSR incidence and influencing factor analysis of DFIG-based series-compensated transmission system in Guyuan farms, High Voltage Engineering, 43, 1, pp. 321-328, (2017)
  • [4] WANG Yijun, DU Wenjuan, WANG Haifeng, Et al., Review on small signal stability analysis of large-scale wind power collection system, Power System Technology, 46, 5, pp. 1934-1946, (2022)
  • [5] ZHANG Jiajun, ZHANG Xinyan, GAO Liang, Et al., Early warning of sub-synchronous oscillation based on time-frequency characteristics of oscillatory components, Electrical Measurement & Instrumentation, 57, 19, pp. 21-26, (2020)
  • [6] WANG Yuhong, WANG Hongyu, YU Guangyuan, Et al., Sub-synchronous oscillation detection and modal parameter identification method based on synchrophasor, High Voltage Engineering
  • [7] ALI M T, ZHOU D, SONG Y P, Et al., Analysis and mitigation of SSCI in DFIG systems with experimental validation, IEEE Transactions on Energy Conversion, 35, 2, pp. 714-723, (2020)
  • [8] MA Ningning, XIE Xiaorong, KANG Pengpeng, Et al., Wide-area monitoring and analysis of subsynchronous oscillation in power systems with high-penetration of wind power, Proceedings of the CSEE, 41, 1, pp. 65-74, (2021)
  • [9] ZHANG Min, SHEN Jian, HOU Mingguo, Et al., Discussion on on-line identification and warning of subsynchronous oscillation for phasor measuring unit, Automation of Electric Power Systems, 40, 16, pp. 143-146, (2016)
  • [10] WANG Maohai, GAO Xun, WANG Bei, Et al., Online early-warning of sub-synchronous oscillations based on wide area measurement system, Automation of Electric Power Systems, 35, 6, pp. 98-102, (2011)