Design of Wide Area Additional Damping Controller for Doubly Fed Wind Farms Considering Time Delays

被引:0
|
作者
Ma Y. [1 ]
Huo Y. [1 ]
Li X. [1 ]
Zheng L. [1 ]
Zhao S. [1 ]
机构
[1] School of Electrical and Electronic Engineering, North China Electric Power University, Baoding
关键词
Active disturbance rejection control; Doubly fed wind farm; Low frequency oscillation; Smith predictor; Time-delay system;
D O I
10.19595/j.cnki.1000-6753.tces.181746
中图分类号
学科分类号
摘要
A wide-area additional damping controller for doubly-fed wind farms based on Smith predictor-active disturbance rejection control (SP-ADRC) is proposed to solve the time-delay problem of wide-area additional damping control of wind farms in interconnected power grids. The real-time estimation of uncertain time-delay is realized by using fading memory recursive least squares method. On this basis, the influence of time-delay on closed-loop control in power system is reduced by using Smith predictor. It overcomes the defect that the control effect of traditional ADRC controller becomes worse in time-delay system, and retains the advantages of active estimation and compensation for uncertainties of ADRC. Finally, a new England 10-generator 39-bus system with wind farms is tested. The simulation results show that the proposed wide-area additional damping controller can effectively suppress the low-frequency oscillation. © 2020, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:158 / 166
页数:8
相关论文
共 22 条
  • [1] Miao Z., Fan L., Osborn D., Et al., Control of DFIG-based wind generation to improve interarea oscillation damping, IEEE Transactions on Energy Conversion, 24, 2, pp. 415-422, (2009)
  • [2] Tsourakis G., Nomikos B.M., Vournas C.D., Contribution of doubly fed wind generators to oscillation damping, IEEE Transactions on Energy Conversion, 24, 3, pp. 783-791, (2009)
  • [3] Aboul-Ela M.E., Sallam A.A., Mccalley J.D., Et al., Damping controller design for power system oscillations using global signals, IEEE Transactions on Power Systems, 11, 2, pp. 767-773, (1996)
  • [4] Wu H., Tsakalis K.S., Heydt G.T., Evaluation of time delay effects to wide-area power system stabilizer design, IEEE Transactions on Power Systems, 19, 4, pp. 1935-1941, (2004)
  • [5] Zhang Z., Hu Z., Liu Y., Additional robust damping control of large scale DFIG-based wind power generation system with wide-area signals' time-varying delay influence, Transactions of China Electrotechnical Society, 29, 4, pp. 246-255, (2014)
  • [6] Wang S., Meng X., Chen T., Wide-area control of power systems through delayed network communication, IEEE Transactions on Control Systems Technology, 20, 2, pp. 95-103, (2012)
  • [7] Yao W., Jiang L., Wen J., Et al., Wide-area damping controller of FACTS devices for inter-area oscillations considering communication time delays, IEEE Transactions on Power Systems, 29, 1, pp. 318-329, (2013)
  • [8] Ma Y., Zhang J., Jiang Y., Et al., Additional robust damping control of wide-area power system with multiple time delays considered, Transactions of China Electrotechnical Society, 32, 6, pp. 58-66, (2017)
  • [9] Yao W., Wen J., Cheng S., Et al., Design of wide-area supplementary damping controller of SVC considering time delays, Transactions of China Electrotechnical Society, 27, 3, pp. 239-246, (2012)
  • [10] Li T., Wu M., He Y., Multi-objective design of FACTS damping controller based on WAMS with signal transmission delay, Transactions of China Electrotechnical Society, 29, 8, pp. 227-234, (2014)