Arc-quenching ability detection of a high voltage vacuum circuit breaker based on switching and closing current

被引:0
|
作者
Sun H. [1 ]
Wang B. [2 ]
机构
[1] College of Electrical and Electronic Engineering, Shandong University of Technology, Zibo
[2] State Key Lab of Control and Simulation of Power Systems and Large-scale Generation Equipment, Department of Electrical Engineering, Tsinghua University, Beijing
基金
中国国家自然科学基金;
关键词
Arc current; Electrical quantity; High voltage vacuum circuit breaker; On-line inspection; Vacuum interrupter;
D O I
10.19783/j.cnki.pspc.210321
中图分类号
学科分类号
摘要
The degradation of the arc extinguishing performance of high-voltage vacuum circuit breakers can easily lead to the generation of continuous arcs, damage to the contact surface and delay of the opening and closing time. In severe cases, a breakdown and explosion may occur. Therefore, research on monitoring the arc extinguishing performance of high voltage vacuum circuit breakers is important. Existing research methods for the arc extinguishing performance of high voltage vacuum circuit breakers consist mainly of measuring the vacuum degree of the arc extinguishing chamber, but there are problems such as long measurement period and inability to guarantee air tightness. The arc extinguishing principle in the arc extinguishing chamber is analyzed. Obtaining the arc extinguishing level in the chamber can be inverted using the influence of the arc resistance on the attenuation characteristics of the arc current when the medium is restored. Using this, the arc current trend item is extracted as the representative quantity of the arc extinguishing ability. An online detection method for the arc extinguishing ability of the high voltage vacuum circuit breaker based only on electrical quantities is proposed. This has the advantages of fast real-time monitoring and safety of measurement. The effectiveness of the method is verified by field measured data and digital simulation. © 2022 Power System Protection and Control Press.
引用
收藏
页码:102 / 109
页数:7
相关论文
共 28 条
  • [1] LIU Jian, ZHANG Zhihua, WU Shuilan, Et al., Fault processing with coordination of primary equipments and secondary devices, Power System Protection and Control, 47, 20, pp. 1-6, (2019)
  • [2] CHEN Lei, HE Huiwen, WANG Lei, Et al., Fault isolation method of a hybrid HVDC system based on the coordination of a fault current limiter and a DC circuit breaker, Power System Protection and Control, 48, 19, pp. 119-127, (2020)
  • [3] CHENG Mengzhu, ZHANG Xinhui, XU Mingming, Et al., Location method of an active distribution network fault section based on multi-target weighted grey target decision, Power System Protection and Control, 49, 11, pp. 124-132, (2021)
  • [4] KHAN W A, BI T, JIA K., A review of single phase adaptive auto-reclosing schemes for EHV transmission lines, Protection and Control of Modern Power Systems, 4, 3, pp. 205-214, (2019)
  • [5] ZENG Xianghao, ZHANG Haichuan, LIAO Minfu, Et al., Restrictive asynchronous breaking strategy of multi-break VCB with fiber controlled module, High Voltage Apparatus, 57, 2, pp. 1-6, (2021)
  • [6] ZHANG Jiang, Research on vacuum degree online detection system based on AVR singlechip, (2011)
  • [7] (1986)
  • [8] MERCK W E H, DAMSTRA G C., Methods for estimation of the vacuum status in vacuum circuit breakers, IEEE Transactions on Dielectrics and Electrical Insulation, 6, 4, pp. 400-403, (1999)
  • [9] MEI Kaifeng, Inspection method of vacuum degree of vacuum interrupter, Rural Electrification, 11, pp. 34-34, (2001)
  • [10] JIN Zhiming, Technical research on vacuum life assessment based on the pulse magnetic discharge method, (2014)