Time-varying Subsynchronous Oscillation Mitigation Strategy for DFIG Wind Farms Based on Improved Adaptive Notch Filter

被引:0
|
作者
Wu X. [1 ]
Xu S. [2 ]
Feng S. [1 ]
Fan L. [3 ]
Gu W. [3 ]
机构
[1] School of Electrical Engineering, Southeast University, Jiangsu Province, Nanjing
[2] Jiangsu Provincial Key Laboratory of Smart Grid Technology and Equipment (Southeast University, Jiangsu Province, Nanjing
[3] Jiangsu Frontier Electric Technology Co., Ltd., Jiangsu Province, Nanjing
基金
中国国家自然科学基金;
关键词
adaptive notch filter; doubly-fed induction generator (DFIG); installation location; rotor-side converter; subsynchronous oscillation;
D O I
10.13334/j.0258-8013.pcsee.222603
中图分类号
学科分类号
摘要
Subsynchronous control interaction (SSCI) may be triggered when DFIG-based wind farms are connected to the grid via series-compensated capacitors, which seriously threatens the safe and stable operation of the system. Embedding notch filters into the DFIG converter controllers can mitigate SSCI effectively. However, the fixed-parameter notch filter is difficult to adapt to the time-varying frequency characteristic of the subsynchronous oscillation in the actual system. To address the issue, a time-varying subsynchronous oscillation mitigation strategy based on the improved adaptive notch filter for DFIG-based wind farms is proposed in this paper. First, effects on blocking the subsynchronous oscillation component are analyzed when the ANF is installed at different positions of the rotor-side converter (RSC), and the best installation location of the ANF is determined. Second, the overall control framework is designed, and the strategy for ANF center frequency updating based on measurement data is developed. Finally, considering multiple influential factors such as wind speed, number of wind turbines, reactive power output, grid topology, etc., the performance of the proposed control strategy in mitigating subsynchronous oscillations with time-varying frequency is verified. Compared with the existing methods, the proposed method is independent of the accurate mathematical model of the system and presents stronger robustness and adaptability. © 2024 Chin.Soc.for Elec.Eng.
引用
收藏
页码:1836 / 1847
页数:11
相关论文
共 40 条
  • [1] WU Xi, WANG Mengting, SHI Xingyu, SSO supplementary damping control method for DFIG based on model-free adaptive control[J], Proceedings of the CSEE, 42, 10, pp. 3601-3613, (2022)
  • [2] LI Penghan, WANG Ziqiang, WANG Jie, Subsynchronous control interaction mitigation strategy based on fractional-order sliding mode control for DFIG-based wind farm[J], Proceedings of the CSEE, 40, 3, pp. 897-910, (2020)
  • [3] ZHANG Xu, XIE Xiaorong, LIU Hui, Design and RTDS test of the grid-side subsynchronous damping controller[J], Proceedings of the CSEE, 38, 22, pp. 6503-6510, (2018)
  • [4] CHEN Jian, DU Wenjuan, WANG Haifeng, A method of locating the power system subsynchronous oscillation source unit with grid-connected PMSG using deep transfer learning[J], Transactions of China Electrotechnical Society, 36, 1, pp. 179-190, (2021)
  • [5] LI Penghan, WANG Jie, WU Fei, Sub-synchronous control interaction mitigation for DFIGs by sliding mode control strategy based on feedback linearization[J], Transactions of China Electrotechnical Society, 34, 17, pp. 3661-3671, (2019)
  • [6] XIE Xiaorong, HE Jingbo, MAO Hangyin, New issues and classification of power system stability with high shares of renewables and power electronics [J], Proceedings of the CSEE, 41, 2, pp. 461-475, (2021)
  • [7] LIU Qihui, HONG Chenwei, PANG Simin, Analysis and adjustment method of doubly-fed fan control parameters on subsynchronous oscillation based on impedance elastic sensitivity[J], Transactions of China Electrotechnical Society, 37, 14, pp. 3528-3541, (2022)
  • [8] CHEN Aikang, Da XIE, ZHANG Daming, PI parameter tuning of converters for sub-synchronous interactions existing in grid-connected DFIG wind turbines[J], IEEE Transactions on Power Electronics, 34, 7, pp. 6345-6355, (2019)
  • [9] MA Jing, SHEN Yaqi, DU Yanling, Overview on active damping technology of wind power integrated system adapting to broadband oscillation[J], Power System Technology, 45, 5, pp. 1673-1686, (2021)