Influence of Different Layout Methods on Artificial Pollution Flashover Characteristics of AC Insulator Strings

被引:0
|
作者
Jiang X. [1 ]
Ren X. [1 ]
Han X. [1 ]
Hou L. [1 ]
Huang Y. [1 ]
机构
[1] State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing
来源
Ren, Xiaodong (xdrcqu@163.com) | 1600年 / China Machine Press卷 / 35期
关键词
Artificial pollution; Electric field distribution; Flashover characteristics; Insulator string; Inverted T type;
D O I
10.19595/j.cnki.1000-6753.tces.181855
中图分类号
O441.1 [电学]; TM12 [];
学科分类号
摘要
The arrangement of insulator strings has an effect on its pollution flashover characteristics. A new arrangement of insulator strings-inverted T-type arrangement, is proposed in this paper. The electric field distribution is simulated and the pollution flashover characteristics are tested in an artificial climate chamber. The results show that the inverted T-type arrangement can greatly improve the flashover voltage of insulator string pollution, the highest pollution flashover voltage of insulator string under the “4+4” inverted T-type arrangement is up to 14.9%, and the flashover voltage of inverted T-type arrangement increases with the increase of the insulator number in the horizontal tensile part. The discharge process of inverted T-type insulator strings is different from that of normal suspension strings, that is, local arcs are produced at the high and low voltage ends of the suspension strings and develop to the middle, while it is difficult for the horizontal tension strings to produce arcs during discharge process. © 2020, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:896 / 905
页数:9
相关论文
共 26 条
  • [1] Shu L., Mao F., Jiang X., Et al., Comparison of the DC pollution flashover perfor-mances among composite insulators and porcelain and glass insulators, Proceedings of the CSEE, 27, 36, pp. 26-30, (2007)
  • [2] Wang L., Wang C., Li Q., Et al., Safety coefficient of composite insulators tension strings for 500kV AC transmission lines, High Voltage Engineering, 38, 1, pp. 9-15, (2012)
  • [3] Zhang F., Song L., Li R., Et al., Influence of the suspension modes on pollution flashover performance for ±800kV composite insulators under high altitudes condition, High Voltage Engineering, 38, 12, pp. 3166-3170, (2012)
  • [4] Su Z., Liang X., Important correction factors in HVDC line insulation selection, Proceedings of the 14th International Symposium on High Voltage Engineering, pp. 1-4, (2005)
  • [5] Alston L.L., Zoledziowski S., Growth of discharges on polluted insulation, Proceedings of the Institution of Electrical Engineers, 110, 7, pp. 1260-1266, (1963)
  • [6] Liu Y., Jiang X., Shu L., Et al., Influence of characterizing shed configuration parameters of composite insulators on icing flashover perfor-mance, Transactions of China Electrotechnical Society, 29, 8, pp. 319-326, (2014)
  • [7] Mizuno Y., Kusada H., Naitio K., Effect of climatic conditions on contamination flashover voltage of insulators, IEEE Transactions on Dielectrics and Electrical Insulation, 4, 3, pp. 286-289, (1997)
  • [8] Li Z., Cui J., Zhou Y., Et al., Influence of insulator installation from on its pollution flashover voltage, Power System Technology, 29, 8, pp. 52-55, (2005)
  • [9] Chen Q., Konrad A., A review of finite element open boundary techniques for static and quasi-static electromagnetic field problems, IEEE Transactions on Magnetics, 33, 1, pp. 663-676, (1997)
  • [10] Tang C., Liang X., Operation and natural contamination test of DC composite insulators abroad, Power System Technology, 23, 9, (1999)