An Adaptive Reclosure Method for Hybrid Cascade Multi-terminal HVDC Circuit Breaker Based on Two-terminal Voltage of DC Circuit Breaker

被引:0
|
作者
Chen Z. [1 ]
Zhou Z. [1 ]
Wang X. [1 ]
Du D. [1 ]
Wen W. [2 ]
Yang L. [3 ]
Guo Y. [1 ]
Cao H. [1 ]
机构
[1] State Key Laboratory for Power Grid Safety and Energy Conservation (China Electric Power Research Institute), Haidian District, Beijing
[2] College of Electrical Automation and Information Engineering, Tianjin University, Nankai District, Tianjin
[3] State Grid Corporation of China, Xicheng District, Beijing
来源
关键词
Composite DC circuit breaker; Hybrid cascade multi-terminal HVDC; Reclosure method;
D O I
10.13335/j.1000-3673.pst.2019.0281
中图分类号
学科分类号
摘要
Hybrid cascade multi-terminal HVDC technology is one of the important development directions of UHVDC transmission in the future, and its reclosure strategy is an important factor related to reliable operation of HVDC system. Firstly, the fault characteristics of hybrid cascade multi-terminal HVDC transmission lines are analyzed, and then the application of combined HVDC circuit breaker in hybrid cascade multi-terminal HVDC transmission is studied. On this basis, an adaptive reclosure method of DC circuit breaker based on the voltages at both ends of DC circuit breaker is proposed. A typical hybrid cascade multi-terminal DC transmission model with composite DC circuit breakers is built on PSCAD/EMTDC, and the reclosure strategy is verified. © 2019, Power System Technology Press. All right reserved.
引用
收藏
页码:2623 / 2631
页数:8
相关论文
共 16 条
  • [1] Liang X., Zhang P., Chang Y., Recent advances in high-voltage direct-current power transmission and its developing potential, Power System Technology, 36, 4, pp. 1-9, (2012)
  • [2] Xu Z., Wang S., Li N., Et al., A LCC and MMC series hybrid HVDC topology suitable for bulk power over head line transmission, Power System Technology, 40, 1, pp. 55-63, (2016)
  • [3] Zhao C., Li T., Yu L., DC pole-to-ground fault characteristic analysis and converter fault recovery strategy of MMC-HVDC, Proceedings of the CSEE, 34, 21, pp. 3518-3526, (2014)
  • [4] Han L., Bai X., Chen B., Et al., Control and protection system design of Zhangbei±500kV converter station in VSC-HVDC power grid, Electric Power Construction, 38, 3, pp. 42-47, (2017)
  • [5] Zhang J., Xiang W., Lin W., Et al., DC fault protection of VSC-HVDC grid based on hybrid MMC and DC switch, Electric Power Construction, 38, 8, pp. 52-58, (2017)
  • [6] Wang Y., Liu J., An enhanced MMC-HVDC topology and system recovery strategy for DC fault protection, Power System Technology, 39, 8, pp. 2312-2319, (2015)
  • [7] Li B., He J., Li Y., Et al., Novel restart scheme of DC fault for flexible DC transmission system, Automation of Electric Power Systems, 41, 12, (2017)
  • [8] Song G., Wang T., Zhang C., Et al., Adaptive auto-reclosing of DC line based on characteristic signal injection with FB-MMC, Power System Technology, 43, 1, pp. 149-156, (2019)
  • [9] Wang S., Bi T., Li W., Et al., A fast bipolar permanent fault identification approach for MMC-MTDC lines, Renewable Energy Resources, 35, 1, pp. 43-49, (2017)
  • [10] Wang S., Bi T., Jia K., Single terminal fault location for MMC-HVDC transmission line using active pulse, Transactions of China Electrotechnical Society, 32, 1, pp. 12-19, (2017)